HomeMy WebLinkAbout20250972 33 Phila St. Herbies Burgers Signage & Exhaust NOD
Page 1 of 1
Tamie Ehinger, Chair
Rob DuBoff, Vice Chair
Chris Bennett
Leslie DiCarlo
Jeff Gritsavage
Geoff Wood
Karen Cavotta
Alison Dockum, Alternate
Christina Abele, Alternate
CITY OF SARATOGA SPRINGS
D ESIGN R EVIEW B OARD
❖
City Hall - 474 Broadway
Saratoga Springs, New York 12866
Tel: 518-587-3550 x.2517
www.saratoga-springs.org
NOTICE OF DECISION
In the matter of the application
#20250972
33 Phila St. Herbie’s Burgers Signage & Exhaust
33 Phila St.
Saratoga Springs, New York 12866
involving Historic review of wall mounted signage within the Urban Core (UC) District, tax parcel # 165.68-1-2, within
the City of Saratoga Springs.
In accordance with 6 NYCRR Part 617, the Design Review Board classifies this request as a SEQR:
Type II action – exempt from further SEQR review
And, in accordance with the objectives, standards and guidelines contained in the Unified Development Ordinance
Article 240-13.9 Architectural Review Applicability and Approval Standards, the Design Review Board issues the
following decision on November 19, 2025:
Approve the project with the following conditions:
Exhaust fan installation is approved; applicant to return for approval on signage
Record of vote:
motion to approve made by G Wood, seconded by J Gritsavage : passed 6-0
In favor: TEhinger, CBennett, LDiCarlo, JGritsavage, K Cavotta, G Wood
As a result of this decision, the applicant:
may proceed with the portions of the proposed project as approved
Please contact the Building Department to verify permit requirements.
Chair Received by Accounts
cc: Building Department
Accounts Dept.
Applicant/Agent
PLENUM FIRE SUPPRESSION SYSTEM NOZZLES & TANK
INSTALLER SHALL VERIFY TANKSIZE WITH MANUFACTURER.
TANK SIZE
PROTEX II OR
EQUAL)
1/2 SCH. 40 BLKS STL.
ANSUL SYSTEM
CONTROL CENTER 3.0
GAL. TANK
1.6 GALLON
3.0 GALLON
4.6 GALLON
4.6 GALLON
6.0 GALLON
6.0 GALLON
MAX# FLOW
POINTS
5
10
15
15
20
20
CLASS, WET CHEMICAL MA.
30 FT FROM COOKING AREA
REMOTE PULL STATION
MIL. 12 FT. FROM HOOD
AUTOMATIC SHUT-OFF
SOLENOID
CONTROLS
ANSUL SYSTEM & COMPONENTS TO COMPLY WITH NFPA 17A & NFPA 96 AND ALL
COMPONENTS U. L. APPROVED.
ALL WIRING AND ELECTRICAL EQUIPMENT SHALL COMPLY W/ NPFA 70 AND THE
NATIONAL ELECTRIC CODE.
PLUMBER TO INSTALL GAS SHUT-OFF Valve w/ TIE TO FIRE SUPPRESSION SYSTEM.
SUPPRESSION SYSTEM TIED TO ALARM SYSTEM w/ MICRO-SWITCH BY ALARM CONTRAC-TOR
FIRE EXTINGUISHERS
CLASS A-B-C EXTINGUISHERS SHALL BE CONSPICUOUSLY LOCATED & READILY ACCESSIBLE.
INSTALLED IN ACCORDANCE w/ NFPA REQUIREMENTS.
CLASS K EXTINGUISHERS SHALL BE PROVIDED FOR ALL AREAS WITH COOKING EQUIP-MENT
AND COMBUSTIBLE COOKING MEDIA IN ACCORDANCE WITH NFPA REQUIRE-MENTS.
CONTRACTOR TO VERIFY ALL
PIPING SIZES WITH APPLI-ANCE
MANUF. SPECS.
ALL APPLIANCES HAVE
INDIVIDUAL GAS SHUT-OFF
VALVES AT APPLIANCE
GAS PIPING NOTES:
1. GAS PIPING SHALL BE BLACK STEEL SHC.
40 OR AS PERMITTED BY CODE
2. PIPING CONNECTIONS SHALL BE THREAD-ED
UNLESS OTHERWISE PERMITTED BY
CODE.
3. ALL GAS BURNING EQUIPMENT SHALL BE
INSTALLED PER NFPA 54, NFPA 58, NFPA 96
4. ALL APPLIANCES HAVE INDIVIDUAL GAS
SHUT-OFF VALVES AT THE APPLIANCE.
MAX. PIPE
VOLUME
MILLILITERS)
1500
1910
3400
2600
4215
3465
MAX. VOLUME ALLOWED
BETWEEN FIRS & LAST
NOZZLE (MILLILITERS)
400
1125
3000
2000
1688/SIDE
1313/ SIDE
4
2
I
F
O
V
E
R
40
W
T
1/2 SCH. 40 BLKS STL.
1/2 SCH. 40 BLKS STL.
42" - 48" ABOVE FIN.FL.
PORTABLE EXTINGUISHER "K"
NOZZLE HEIGHT SHALL BE MIN. 12" MAX. 50" FROM COOKING EQUIPMENT .
MECHANICAL PULL STATION SHALL BE LOCATED 10' - 25' FROM THE RANGE HOOD.
TOP OF EXTINGUISHERS MA 60" ABOVE FLOOR BOTTOM MIN 4" ABOVE FLOOR ,&
DU
C
T
GRILL
36"
HO
R
I
Z
O
N
T
A
L
INSTALLER: PROTECT-IT FIRE
NEW YORK OCT - 2025
NEW EXHAUST HOOD
33 & 36 Phila St,
Saratoga Springs, NY 12866
PROJECT
HERBIE'S BURGES SARATOGA