HomeMy WebLinkAbout20240367 186 Circular Two Story Addition PlansSTRUCTURAL NOTES GENERAL NOTES CONSTRUCTION DOCUMENTS 1. ALL STRUCTURAL DESIGN ELEMENTS AND COMPONENTS ARE DERIVED FROM APPLICABLE PROVISIONS OF THE 2020 INTERNATIONAL RESIDENTIAL CODE AS ADOPTED BY NEW YORK STATE UNLESS OTHERWISE NOTED ON THE DRAWINGS. WHERE NOTED, CERTAIN STRUCTURAL MEMBERS MAY BE DESIGNED USING: -THE AMERICAN FOREST AND PAPER ASSOCIATION (AF&PA) NATIONAL DESIGN SPECIFICATIONS (NDS) -MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES (ASCE 7) 2. NO GEOTECHNICAL EVALUATION HAS BEEN DONE IN CONNECTION WITH THE FOUNDATION DESIGN. IN ACCORDANCE WITH TABLE R401.4.1 THE LOAD BEARING PRESSURE USED FOR DESIGN OF ALL FOUNDATION SUPPORTING ELEMENTS IS 2000 PSF FOR SAND , SILTY SAND, CLAYEY SAND, SILTY GRAVEL AND CLAYEY GRAVEL. IF OTHER SOIL TYPES ARE ENCOUNTERED IN EXCAVATION OR IF THE ACTUAL SOIL BEARING PRESSURE IS QUESTIONABLE, CONSULT WITH ARCHITECT/ENGINEER 3. IT IS NOT ANTICIPATED THAT GROUND WATER WILL BE ENCOUNTERED IN EXCAVATIONS. FOOTINGS SHALL NOT BE POURED WITHIN SEASONAL HIGH GROUND WATER ZONES. CONSULT ARCHITECT/ ENGINEER IF HIGH GROUND WATER IS ENCOUNTERED STRUCTURAL DESIGN LOADS: LIVE LOADS SLEEPING ROOMS....................30 PSF NON -SLEEPING ROOMS ........... 40 PSF GROUND SNOW LOAD..............50 PSF FRAMING NOTES 1. ALL WINDOW DOOR HEADERS TO BE TWO (2) 2x1O'S UNLESS OTHERWISE NOTED (SEE FRAMING PLANS). ALL HEADERS IN OPENINGS 72" OR MORE MUST BE SUPPORTED BY DOUBLE JACK STUDS. 2. ALL FRAMING TO BE 8" MINIUMUM ABOVE FINISHED GRADE. 3. ALL FRAMING TO BE FASTENED IN ACCORDANCE WITH TABLE R602.3(1) OF THE 2020 INTERNATIONAL RESIDENTIAL CODE AS ADOPTED BY NYS. 4. ALL EXTERIOR WALLS TO BE 2x6 (9) 16" O.C. WITH R-21 FIBERGLASS BATT INSULATION UNLESS OTHERWISE NOTED. ALL INTERIOR PARTITIONS TO BE 2x4 @ 16" O.C. UNLESS NOTED OTHERWISE. 5. (NA) INSTALL METAL OR WOOD BRIDGING AT THE MIDPOINT OF ALL JOIST SPANS EXCEPT WHERE NOTED. NOT REQUIRED WITH ENGINEERED JOISTS. 6. PROVIDE DOUBLE FRAMING AROUND ALL FLOOR OPENINGS AND UNDER ALL BEARING PARTITIONS PARALLEL WITH JOIST DIRECTION. MODIFY FLOOR FRAMING AS REQUIRED TO ACCOMODATE PLUMBING AND MECHANICAL REQUIREMENTS WITHOUT AFFECTING STRUCTURAL INTEGRITY. 7. INSPECT ALL LUMBER FOR DEFECTS BEFORE INSTALLING . DISCARD ANY SUCH LUMBER. ALL RAFTERS AND FLOOR JOISTS TO BE INSTALLED WITH CROWN UP. 8. ALL FRAMING STUDS TO BE #2 CONSTRUCTION GRADE UNLESS NOTED OTHERWISE. RAFTERS AND JOISTS TO BE SPF NO. 2 OR BETTER. DO NOT CHANGE SIZE OR SPACING OF ANY STRUCTURAL ELEMENTS WITHOUT ENGINEER'S WRITTEN CONSENT. fb=1 ,1 50psi. E=1,400,000 psi (FOR REPETITIVE USE MEMBERS) 9. PROVIDE CONCEALED WOOD BLOCKING IN ALL WALLS THAT REQUIRE SURFACE MOUNTED ITEMS SUCH AS: CABINETRY, HOSE BIBS, FIREPLACE MANTELS, MOLDING, RAILINGS, TOWEL BARS, ETC. 10. PROVIDE FIRESTOPPING WHERE REQUIRED BY THE 2020 INTERNATIONAL RESIDENTIAL CODE AS ADOPTED BY NEW YORK STATE. 11. ALL DIMENSIONS ARE TAKEN TO ROUGH FRAMING UNLESS OTHERWISE NOTED. 12. (NA) ROOF TRUSSES TO BE CERTIFIED BY TRUSS MAN UFACTURER.CONTRACTOR TO COORDINATE AND CONSULT WITH ARCHITECT/ENGINEER PRIOR TO TRUSS FABRICATION IF TRUSSES ARE TO BE USED IN FRAMING. 13. 1.9E MICRO -LAM LUMBER DESIGN STRESS - E+1,900,000 psi, fb = 2,600 psi. ENERGY NOTES 1. TO THE BEST OF MY KNOWLEDGE, BELIEF AND PROFESSIONAL JUDGEMENT THE ATTACHED PLANS AND SPECIFICATIONS ARE IN COMPLIANCE WITH CHAPTER 11 OF THE 2020 INTERNATIONAL RESIDENTIAL CODE AS ADOPTED BY NEW YORK STATE. 1. ALL GENERAL NOTES ON THIS SHEET APPLY TO ALL DRAWINGS. 2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS AND SEQUENCING AND SHALL BE RESPONSIBLE TO THE OWNER FOR PROVIDING A SAFE WORK ENVIROMENT DURING THE CONSTRUCTION PERIOD. 3. THESE DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS FOR CONSTRUCTION SAFETY. THE CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND CONSTRUCTION OF ALL TEMPORARY SUPPORTS. BRACE BUILDING UNTIL ALL STRUCTURAL ELEMENTS NEEDED FOR STABILITY ARE INSTALLED. 4. THIS BUILDING HAS BEEN DESIGNED IN COMPLIANCE WITH THE REQUIREMENTS OF THE CURRENT RESIDENTIAL ENERGY CONSERVATION CONSTRUCTION CODE OF NEW YORK STATE AND THE RESIDENTIAL CONSTRUCTION CODE OF NEW YORK STATE. APPLICABLE CODE IS IRC 2020 VERSION AS ADOPTED BY NYS. 5. ALL MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTRUCTION AND RECOMMENDATIONS. THE CONTRACTOR SHALL DELIVER TO THE OWNER ALL MANUFACTURER'S WARRANTIES, GUARANTEES, LITERATURE AND OPERATING INSTRUCTIONS FOR ALL PRODUCTS AND EQUIPMENT. 6. DIMENSIONS AND DETAILS ARE BASED ON THE BEST AVAILABLE INFORMATION AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFING FIELD DIMENSIONS BEFORE ORDERING MATERIALS AND PREFABRICATED ITEMS. 7. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED MATERIALS AND COMPONENTS OF NON -SPECIFIED ITEMS, SUCH AS: NAILS, FLASHING, ETC. TO PROVIDE A COMPLETE CONSTRUCTION PROJECT, SOUND AND WEATHER TIGHT AND TO COMPLY WITH CURRENT STANDARDS OF QUALITY CONSTRUCTION. 8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSPECTING HIS OWN WORKMANSHIP TO THE EXTENT THAT SATISFIES THE OWNER. 9. ALL WORK SHALL BE PERFORMED IN THE BEST AND MOST PROFESSIONAL MANNER BY MECHANICS SKILLED IN THEIR RESPECTIVE TRADES. 10. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN FIELD AND REPORT ALL DISCREPANCIES TO THE ARCHITECT/ ENGINEER FOR RESOLUTION. 11. OWNER AND BUILDER SHALL COMPLY WITH THE LAWS , STATUTES AND RULES THAT GOVERN CONSTRUCTION OF THIS RESIDENCE. 12. ALL MEANS AND METHODS OF CONSTRUCTION ARE THE RESPONSIBILTY OF THE CONTRACTOR, INCLUDING BUT NOT LIMITED TO SHORING, SUPPORT AND BRACING OF EXISTING STRUCTURES AS REQUIRED FOR THE WORK. CONSULT WITH THE ARCHITECT/ENGINEER WHERE NECESSARY. 13. COORDINATE SELECTION OF ALL MATERIALS AND PRODUCTS NOT SPECIFICALLY CALLED OUT IN THE SPECIFICATIONS AND ON THE DRAWINGS SUCH AS: PAINTING MATERIALS AND COLORS, INTERIOR FINISHES, LIGHT FIXTURES, CABINETRY, APPLIANCES AND ACCESSORIES, WITH THE OWNER. 14. THE CONTRACTOR SHALL PROVIDE A ONE-YEAR GUARENTEE OF MATERIALS AND WORKMANSHIP FOR ALL WORK UNDERTAKEN, COMMENCING AT SUBSTANTIAL COMPLETION. THE WORK IS ALSO SUBJECT TO APPLICABLE PROVISIONS OF THE HOME WARRANTY ACT OF NEW YORK STATE. ELECTRICAL NOTES 1. ALL WORK SHALL COMPLY WITH THE 2020 INTERNATIONAL RESIDENTIAL CODE AS ADOPTED BY NEW YORK STATE. 2. THE ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF ALL TRADES AND ALL WORK SHALL BE PERFORMED BY MECHANICS SKILLED IN THE ELECTRICAL TRADE. 3. ALL WIRING SHALL BE CONCEALED ABOVE CEILINGS OR WITHIN WALLS UNLESS NOTED OTHERWISE. ALL EXPOSED WIRING SHALL BE LOCATED SO THAT IT IS OUT OF VIEW AS MUCH AS POSSIBLE. ALL EXPOSED CONDUIT SHALL BE DONE IN THE NEATEST AND MOST ORDERLY FASHION. 4.HVAC EQUIPMENT SHALL BE BY OTHERS. COORDINATE WITH HEATING AND PLUMBING CONTRACTORS AND PROVIDE ALL LINE VOLTAGE WIRING AND CONNECTIONS TO THEIR EQUIPMENT AS REQUIRED. 5. GROUND FAULT RECEPTACLES MUST BE PROVIDED PER RESIDENTIAL CODE OF NEW YORK STATE. 6. AFCI RECEPTACLES SHALL BE PROVIDED IN ALL BEDROOMS. 7. MINIMUM OF 75% OF PERMANENTLY INSTALLED LIGHT FIXTURES SHALL BE RATED FOR ENERGY EFFICIENCY. (I.E.: CFL, LED, ETC.) 1. THE ARCHITECT/ENGINEER HAS NOT BEEN RETAINED FOR CONSTRUCTION OBSERVATION OR ADMINISTRATION AND ASSUMES NO RESPONSIBILITY FOR FIELD CHANGES, CONTRACTOR METHODS, MATERIAL SELECTIONS, PRODUCT PERFORMANCE OR WARRANTY OR SAFETY DURING CONSTRUCTION. 2. LAW DOES NOT PERMIT ALTERATIONS TO THESE DOCUMENTS. THE ARCHITECT/ENGINEER MUST APPROVE ANY ALTERATIONS TO THE DRAWINGS. ABSENT SUCH APPROVAL, THE ARCHITECT/ENGINEER IS NOT RESPONSIBLE FOR SUBSTANTIVE CHANGES. 3. THESE PLANS ARE INSTRUMENTS OF SERVICE FOR THE CONSTRUCTION OF ONE BUILDING ONLY AND ARE NOT TO BE COPIED IN ANY FORM WHATSOEVER WITHOUT THE EXPRESS WRITTEN CONSENT OF ARCHITECT/ENGINEER. 4. THE PLANS ARE NOT VALID FOR USE IN OBTAINING A BUILDING PERMIT WITHOUT THE APPLICATION OF THE ORIGINAL "SEAL" AND SIGNATURE OF THE ARCHITECT /ENGINEER 5. THESE DOCUMENTS WERE PREPARED FOR THE CONSTRUCTION OF A SINGLE PROJECT. ANY UNAUTHORIZED USE OF THESE DOCUMENTS IS EXPRESSLY PROHIBITED AND CONSTITUTES THEFT OF SERVICES. FIRE, CARBON MONOXIDE AND SMOKE DETECTION NOTES 1. UNLESS OTHERWISE INDICATED ON THE DRAWINGS, HARD -WIRED SMOKE DETECTING DEVICES MUST BE INSTALLED IN EACH NEW SLEEPING ROOM, OUTSIDE ALL NEW SLEEPING AREAS, ON EACH STORY WITHOUT SLEEPING ROOMS, IN BASEMENTS WITH OR WITHOUT HABITABLE SPACE. NONE ARE REQUIRED IN UNINHABITABLE ATTICS. ALL DETECTORS IN NEW CONSTRUCTION MUST BE INTER -CONNECTED. 2. CARBON MONOXIDE ALARMS IN DWELLING UNITS SHALL BE INSTALLED OUTSIDE OF EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOMS. WHERE A FUEL -BURNING APPLIANCE IS LOCATED WITHIN A BEDROOM OR ITS ATTACHED BEDROOM, A CARBON MONOXIDE ALARM SHALL BE INSTALLED WITHIN THE BEDROOM. 3. SMOKE AND CARBON MONOXIDE ALARMS MUST BE PROVIDED WITH BATTERY BACKUP, EITHER INTERNAL OR REMOTE. 4. HARD -WIRE DETECTING DEVICES MUST BE POWERED FROM A LIGHTING CIRCUIT WITH NO INTERVENING SWITCHES. ELECTRONIC, LOW -VOLTAGE SYSTEMS ARE ALLOWED PROVIDED THE SYSTEM COMPLIES WITH NFPA 72 PLUMBING, HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS: 1. ALL HVAC WORK, EQUIPMENT, ETC. SHALL BE IN ACCORDANCE WITH THE 2020 INTERNATIONAL RESIDENTIAL CODE AS ADOPTED BY NYS. 2. THE HVAC CONTRACTOR SHALL CONDUCT ALL TESTS AND INSPECTIONS OF HIS WORK AS REQUIRED BY THE OWNER AND LOCAL ENFORCEMENT AUTHORITY. 3. THE HVAC CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF ALL OTHER TRADES. 4. ALL WORK SHALL BE PERFORMED BY MECHANICS SKILLED IN THIS MECHANICAL TRADE. 5. THE CONTRACTOR SHALL PROVIDE ALL CONTROL WIRING. ALL CONTROL WIRING SHALL BE CONCEALED FROM VIEW. 6. THE CONTRACTOR SHALL PROVIDE OPERATING AND MAINTENANCE INSTRUCTIONS ON ALL EQUIPMENT TO THE OWNER. INFORMATION SHALL BE BOUND NEATLY AND IN A COMPREHENSIBLE MANNER. 7. THE CONTRACTOR AND THE OWNER SHALL BE RESPONSIBLE FOR THE SPECIFICATION OF ALL HEATING AND VENTILATING EQUIPMENT NOT SPECIFICALLY NOTED ON THESE DRAWINGS. THE HEATING CONTRACTOR SHALL SUBMIT CATALOG CUTS ON ALL HEATING EQUIPMENT AND MATERIALS TO THE OWNER AND/OR GENERAL CONTRACTOR FOR APPROVAL. 8. ALL NEW SPACES SHALL BE PROVIDED WITH EQUIPMENT CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF AT LEAST 68 DEGREES AT A POINT 3 FEET ABOVE THE FLOOR AND 2 FEET FROM EXTERIOR WALLS. 9. PROGRAMMABLE THERMOSTATS SHALL BE PROVIDED. 10. PLUMBING CONTRACTOR SHALL COMPLY WITH THE 2020 INTERNATIONAL RESIDENTIAL CODE AS ADOPTED BY NEW YOUR STATE FOR THE DESIGN AND INSTALLATION OF ALL PLUMBING SYSTEM COMPONENTS. ALL WORK SHALL BE INSPECTED AS REQUIRED DURING CONSTRUCTION AND APPROVED AT THE END OF THE PROJECT BY THE LOCAL ENFORCEMENT AUTHORITY. cov oo IW-JWZ� fN >_ O ¢zg-oul •N z U N'JWaOW � O oc0¢za.a = N E }Wz000a W � I V ZZZ�WV W G 0 fuLj=� N� o W W Z 0 0-1 F.3:mwMet ggFJZUW .� 0000a Z C Lo or) co o W ca -�� _ i Y 0 ~WUa¢O r� > Qa�w m Y w Z 3 O U- a O F w 0) V W � W a 0 START DATE: STAMP: DATE: 05/08/2024 FILE: PAGE CONTENT: NOTES DRAFTER: ENGINEER: JB Ngij�,qY PW PAPER SIZE: SCALE: 22X34 AS NOTED SHEET: 1 OF 5 10'-6"t 8'-2"t � Q ROUGH CUT x8 FLOOR JOISTS Q Wpn ABOVE 16 O.C. NOTE: EXISTING m woo LALLY COLUMNS gym' m VARY BETWEEN W ~ml m FW 2" AND 2.5" IN H_ DIAMETER 00Q �L IL 000 X Q ROUGH CUT 2x8 FLOOR JOISTS ABOVE 16 O.C. Q mw wm m �m F�NEW 3" DIAM. STEEL COLUMN W/ TOP AND xQ BASE PLATES ON A 00U 24"x24"x12" THICK I CONC. FOOTING I L--J 1 ST FLOOR BASEMENT ROUGH CUT 2x8 FLOOR JOISTS ABOVE 16 O.C. ROUGH CUT Q_2x8 FLOOR ABOVE 16 EXISTING 18" Wm� THICK STONE m AND MORTAR FOUNDATION Fw m 00 XQ I 3000 PSI 6" t z0 I V) POURED CONC. F 1 'TF FORMING p OO SYSTEMS' INSTALL: 0 AS PER ° Q I CRAWL SPACE o MANUFACTURER'S .I p I O(D SPECIFICATIONS 0) � -w 0- 1 1 =0 O 1 4 xm m 1 L—------N� --- I FOOTINGS AND WALL OF — NEW FOUNDATION NOT TO EXCEED DEPTH OF EXISTING FOUNDATION OR UNDERMINE IT IN ANY WAY. FIELD VERIFY DEPTH AND SIZE OF REQUIRED BILCO DOOR PRIOR TO PURCHASE OF DOOR. SEE 'BILCO DOOR DETAILS' BELOW ON THIS SHEET. LIP SID 3'-0" 1 _1 6'-6" 16'-0"f PROPOSED ADDITION 12'-6"t ROUGH CUT 2x8 FLOOR JOISTS ABOVE 16 O.C. BASEMENT 3X8 TIMBER ;ARRIER BEAM EW 3" DIAM. STEEL OLUMN W/ TOP AND ASE PLATES ON A 4"x24"x12" THICK ONC. FOOTING 21"x21" BRICK COLUMN TYP. mw ROUGH CUT Wm 2x8 FLOOR JOISTS JOISTS m ABOVE 16 O.C. O.C. FW m T xQ NEW 3" DIAM. STEEL 00 COLUMN W/ TOP AND -- BASE PLATES ON A I I 24"x24"x12" THICK I I CONC. FOOTING i - -�8X8 TIMBER BEAM 2" LALLY 12"x12" COLUMN TYP. BRICK COLUMN PROVIDE 36" WIDE 24" HIGH ACCESS TO NEW CRAWL SPACE FROM EXISTING BASEMENT PARTIAL BRICK WALL EW ��- ��i� ICI �� i� ice- � ®fl _ Iulfulllul ll�lul lll��lul•111 E III I� SM 'ANCE /-HANDLE I H- C� z w m 0 SCALE 1/4" = T-®" I -DIM. ' EI GH f� DIM. 'D' FRAME OPENING WIDTH FOUNDATION ATTACHMENT TO EXISTING — USE NO. 4 EPDXY DOWELS TIED INTO EXISTING FOUNDATION TYP. BASEMENT (CRAWL SPACE) DOOR CLASSIC SERIFS — STEEL SIDED SIZE „A„ (WIDTH) „B„ (LENGTH. „C„ 'HEIGHT) 4T10 (F.D. W) „E„ (F,D. L) 7„ (C.❑.) B 51' 64' 22' 44' 60' 41' C 55" 72' 19 1/2' 48' 67' 45" ❑ 47' 58' 30' 40' 58' 37' SL 51' 43 1/4' 52' 44' 60, 41" DIM. 'A' WIDTH EXISTING FIRST FLOOR PLAN `/ REMOVALS SCALE 1/4" = T-®" Lm REMOVALS ............................. NEW WALLS ........................... NEW FOUNDATION 'TF FORMING SYSTEMS'......... coco00 O Qz()z0W • N z U N :) -i LL w 0Cooaz�a = N E }WzPow% 0. 0 W � V mwz 88w 8W m 0 azO�c9aWm G = � NO W W z c~ gIt g�JZUW C Ln cy) U) W m _ i Y 0 ~WUa¢O r� > Qa�w M � m Z O O LL a O iz W V W a 0 zz Z W >- � o� WZ CO Uwe <<O z Z �Q� �Qc� IL LIJ 0) 0 01 0 0 0 01 (AO(�C� JI�I�Q�(� Ir QLLQ W T VJ START DATE: STAMP: DATE: 05/08/2024 FILE: PAGE CONTENT: FLOOR PLAN DRAFTER: ENGINEER: PJB Ngij�,qYW PAPER SIZE: SCALE: 22X34 AS NOTED SHEET: 20F5 LIGHT AND VENT ROOM REQUIREMENT TABLE (AREA REQUIRED AREA SUBMITTED) RM. AREA REQUIRED REQUIRED SUBMITTED SUBMITTED ROOM SQ. FT. LIGHT VENT LIGHT VENT SQ. FT. SQ. FT. SQ. FT. SQ. FT. UNIT 3 244.5 19.56 9.8 24.2 14.5 BEDROOM FIRST FLOOR 159.1 12.72 6.36 23.56 12.80 BEDROOM DOOR SCHEDULE <( NO. DESCRIPTION W x H DOOR SIZE NOTE: VERIFY DOOR ROUGH OPENING WITH MANUFACTURER 1 6 PANEL DR. 2'-6" x 6'-8" 2 6 PANEL DR. 2'-0" x 6'-8" 3 BI—FOLD DR. 4'-0" x 6'-8" 4 CRAWL SPACE ACCESS DOOR AT BILCO 3'-0" x 5'-6"f FIELD VERIFY WINDOW SCHEDULE - ANDERSEN 400 SERIES NO CODE TYPE ROUGH OPENING GLASS VENT EGRESS ABOVE WXH SQ. FT. SQ. FT. SQ. FT. 1 TW24310 DOUBLE 2'-6 1 /8" x 4'-0 7/8" 6.73 3.64 3.64 48 " DOUBLE HUNG EACH WINDOW EA. UNIT EA. UNIT EA. UNIT 2 TW2662 DOUBLE HUNG 2'-8 1 /8" x 6'-4 7/8" 11.78 6.4 6.4 24" 3 CW145 CASEMENT 2'-4 7/8" x 4'-5 3/8" 8.0 7.5 7.5 MATCH EXISTING 2x8 RAFTERS 16" O.C. 2x12 LEDGER BEAM EXISTING — STRUCTURE THERMAL - ENVELOPE 2x10 LEDGER BEAM - ATTACHED W/ Y2" DIAM. ANCHOR BOLTS 24" O.C. STAGGERED. FLOOR JOIST HANGERS FOR 2x10 FL. JSTS. OPTIONAL 2500 PSI SLAB 4" THICK - CONCRETE 6 MIL POLY VAPOR BARRIER 3 — NO. 4 REBARS 16" WIDE x 8" CONCRETE FOOTINGS UNDISTURBED SOIL, ASSUME SOIL BEARING PRESSURE TO BE 2000 POUNDS PER SQUARE FOOT APPROXIMATE iIRAnF" TYPICAL SECTION SCALE 1/4" = 1'-O" 5/8" CDX PLYWOOD W/H CLIPS MATCH EXISTING ROOF SHINGLES R-38 CLOSED CELL SPRAY FOAM INSULATION BEAM XXXXXX MATCH EXISTING DORMER, FASCIA, AND ALL COMPONENTS OF EXISTING MANSARD ROOF. SALVAGE EXISTING DORMER TO BE REMOVED AND REINSTALLED ON NEW ADDITION IF POSSIBLE. SEE FLOOR PLANS 48" ICE AND SNOW SHIELD, BEGIN AT OVERHANG ONTINUOUS SEALANT ETAL DRIP EDGE OUBLE 2x6 TOP PLATE 2x6 16" O.C. STUD WALL W/R-21 INSUL. AND TYVEK HOUSE WRAP (OPTIONAL ZIP WALL SYSTEM), Y2" CDX PLYWOOD SHEATHING OR 7/6" rewc 3/4" T&G PLYWOOD SUBFLOOR SCREWED, NAILED W/ CONSTRUCTION ADHESIVE ALL EXTERIOR TRIM, IN WOOD TO MATCH EXISTING HOUSE 2x10 RIM JOIST PROVIDE 10" LONG Y2" DIAM. ANCHOR BOLTS 7" EMBEDMENT 48" O.C. AND 12" FROM FOUNDATION CORNERS THROUGH 2x8 P.T. SILL PLATE W/ SILL SEALER. NO. 4 VERTICAL BARS 30" O.C. THE EXPOSED ICF FOUNDATION WILL BE PARGED WITH CEMENT AND COLORED TO MATCH EXISTING GRANITE FOUNDATION COLOR. DAMP PROOFING NO. 30" OF 12" 4 BARS HORIZONTAL O.C., 12" FROM TOP CONCRETE WALL AND FROM TOP OF FOOTING 3000 PSI 6" THICK POURED CONCRETE 'TF FORMING SYSTEMS' WAL 4" PERFORATED DRAIN TILE DRAIN TO DAYLIGHT OR STORM WATER SYSTEM NOTE: INTERIOR TRIM WORK AND FINISHED FLOORS NOT SHOWN ON DRAWINGS SEE 'END OF STEEL BEAM — CONNECTION TO STEEL COLUMN DETAIL — TYPICAL' SHEET 4 OF 5 SEE 'INTERSECTING STEEL - BEAM TO STEEL BEAM CONNECTION DETAIL' SHEET 4 OF 5 BEAM NO END OF FORMER EXTERIOR WALL IN KITCHEN STAIRS: RISER 7.32"-1- RUN 10" NOSING 1" T STAIRS SCALE 1/4n = 1'-O" C W/ PROPOSED D D MI ` E f SCALE 1/4- INSTALL NEW SHOWER EXISTING BEAM ABOVE NEW WALL TO REMAIN 5'-0" LONG VANITY W/ SINK EXPAND AND INFILL EXISTING PASSAGE TO CENTER BETWEEN CLOSETS NEW ARCH 2x4'S 16" O.C. INTER. WALLS TYP fY N NjtWi� 00 IW-JW� fN O azwz6, •N z U m'JwaOw = N E }Wz0ooa W I V zzWV W m �zoc�awai G =� N �OWWzm~ (j) UW .� a) 00- ooQoa z oz 0 0, aH�mi F-LU c Ln � co W m _ i Y 0 ~WUa¢O r� > aaw m Z O O LL a O iz w cl) V W a 0 START DATE: STAMP: DATE: 05/08/2024 FILE: PAGE CONTENT: FLOOR PLAN TYPICAL SECTION SCHEDULES DRAFTER: ENGINEER: PJB Ngij�,qYW PAPER SIZE: SCALE: 22X34 AS NOTED SHEET: 30F5 EXISTING OFFICE — STUDIO CHIMNEY UNIT 3 O (MOST OF UNIT 3 WAS NOT MEASURED AND DETAILED) EXISTING BATH ROOM REMOVE EXISTING WALL AND WINDOW SHOWN DASHED. PROVIDE MIN. 36" LANDING AT TOP OF NEW STAIRS. ABOVE BEAM TO SPAN 4'-5" THIS DIMENSION EXISTING REMOVE EXISTING 'FORMER' OFFICE— EXTERIOR WALL TO THE STUDIO HEIGHT BELOW PROPOSED NEW STAIRS LANDING CLO. p LANDING w STEP 0 p QZ >I J Q0� ow _ wp Qo36" MIN. � PROVIDE HARDWIRE 36" 1N U 0 ® SMOKE DETECTOR W/ BAT. BACKUP -i & CARBON MONOXIDE � W 3 -i DETECTOR STORAGE 34' MIN . --J ROOM00 HIGH HANDRAIL BEAM PROVIDE HARDWIRE ® SMOKE DETECTOR W/ BAT. BACKUP & CARBON MONOXIDE DETECTOR + 3 UNIT 3 EXISTING FRAME FLOOR JOISTS OVER BEDROOM EXISTING STAIRWELL. MATCH EXISTING FLOOR EXISTING SE N �LOOR PLAN C F SCALE 1/4" = 1'-0n (NY) TABLE N1102.1.2 (R402.1.2) INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT CLIMATE ZONE FENESTRATION SKYLIGHT GLAZED CEILING WOOD FRAME MASS FLOOR BASEMENT SLAB CRAWL U-FACTOR U-FACTOR FENESTRATION R-VALUE WALL WALL R-VALUE WALL R-VALUE SPACE SHGC R-VALUE R-VALUE R-VALUE AND DEPTH R-VALUE 5 0.30 NR NR R38 R21 NA NA R15 NA NA 1' I REMOVAL NEW WALL NEW FOur 'TF FORMI FRAME FLOOR JOISTS OVER EXISTING STAIRWELL MATCH EXISTING FLOOR T*\/ED I rl A I BI (FACING FROM SACK OF HOUSE) SCALE 1/4" = 1'-0" 3" DIAM. SCHEDULE 40 STEEL COLUMN 6"x1 /2"x6" STEEL PLATE, 4-3/4" DIAM. M BOLTS END OF STEEL BEAM CONNECTION TO STEEL COLUMN DETAIL - TYPICAL SCALE: NONE BEAM NO. 1 W12x30 4"x4"x1 /2", 8" LONG, STEEL ANGLES WELDED TO WEB OF BOTH INTERSECTING BEAMS CUT FLANGE OF STEEL BEAM AS NECESSARY TO ABUT INTERSECTING STEEL BEAM BEAM NO. 2 W12x22 INTERSECTING STEEL BEAM TO STEEL BEAM CONNECTION DETAIL SCALE: NONE (714 Ni co0 0 IW-JWZ� fN O Qz()z0W • Q) z U co) W IL 0 W � 0co0az�a = N E }WzooOa W I Ca)Z z Z W V W mp�Zco) 10 WWfn T� 30�=W�2et g Q U >1 ZZZ W a) 00 OzWOg =o_a�Z w aoz�z q Y 0 ~ F. I Q O > W a a 3: W it m Y � Z � O LL a 0 iz w cl) V Lu � W a 0 START DATE: STAMP: DATE: 05/08/2024 FILE: PAGE CONTENT: SECOND FL. PLAN, ELEVATION DRAFTER: ENGINEER: JB Ngij�,qY PW PAPER SIZE: SCALE: 22X34 AS NOTED SHEET: 40F5 R D I BOARD' /LENT SIDING r0 MATCH STING COLOR REVEAL OF REST OF THE J SE TYP. � I PROPOSED ADDITION .PRBILCOPOSED DOOR L -Ls LEFT SIDE ELEVATION W/ PROPOSED ADDITION (FACING FROM BACK OF HOUSE) SCALE 1/4" = 1'-0" NOTE: THE ENGINEER MUST BE NOTIFIED IF ANY ITEMS USED/SUBSTITUTED BY CONTRACTOR ARE NOT SPECIFIED ON THE DRAWINGS TABLE R301.20) CLIMATE AND GEOGRAPHIC DESIGN CRITERIA SEISMIC DESIGN CRITERIA SUBJECT TO DAMAGE FROM WEATHERING FROST LINE TERMITE DEPTH C SEVERE 48" MODERATE GROUND SNOW WIND DESIGN SPEED TOPOGRAPHIC SPECIAL WINDBORNE LOAD (MPH) EFFECTS WIND DEBRIS REGION ZONE 50 115 NA NA I NA WINTER ICE BARRIER FLOOD AIR MEAN DESIGN UNDERLAYMENT HAZARDS FREEZING AIR TEMP. REQUIRED INDEX TEMP. —1 YES NA 1500 NA IN �' f �_--- REMOVALS ............................. NEW WALLS ........................... NEW FOUNDATION 'TF FORMING SYSTEMS'......... Z O F 0 _o Q 0 w V) O O � o II I I I PROPOSED ADDITION II I I I u L Z W/ R C)SE D ADDITION SCALE 1/4" = 1'-0- WORK LOCATION t 9 EVolve NY v'f Charging Station a The Residences at Spring Valley VEmm� E Imo_ SCALE: NONE ro.a. �Is' Y� N cco Niu, 00 IW— JWZHfjj O Qz()z0W •N z U N'JW-- Ow fi 0Cooaz�a = N E }WzPow% 0. 0 Lu L: � V mzw 88Lu w 8W m 0 azO�c9aWm G = � N� O W W z�~ gmet gFJZULu W 0 � �^ � QH�� f"W C I-.� l � co QVc.D W to i Y 0 ~WUa¢O r� > Q IL 9L m Y W Z 0 O LL a O iz W 0) o v w � w a 0 START DATE: STAMP: DATE: 05/08/2024 FILE: PAGE CONTENT: ELEVATIONS TABLE, MAP DRAFTER: ENGINEER: JB Ngij�,qY PW PAPER SIZE: SCALE: 22X34 AS NOTED SHEET: 50F5