Regarding: PRELIMINARY GEOTECHNICAL INVESTIGATION
PROPOSED BREWERY/RESTAURANT
3376 SOUTH BROADWAY
SECTION 178, BLOCK 2, LOT 15
SARATOGA SPRINGS, SARATOGA COUNTY, NEW YORK
WHITESTONE PROJECT NO.: GM2321159.Y00
Dear Ms. Morin:
Whitestone Associates Engineering & Geology NY, PLLC (Whitestone) has completed a limited
geotechnical investigation at the above-referenced site. The results of the investigation and
recommendations presented below are based on the soil conditions disclosed from a limited number of
borings performed during Whitestone’s field investigation. The purpose of the investigation was to assess
subsurface conditions within and adjacent to the proposed building areas accessible to track-mounted
drilling equipment and a tracked excavator. Subsequently, cone penetrometer test (CPT) probes were
advanced. Preliminary recommendations for support of the proposed structures and pavements, and
anticipated earthwork requirements are included herein.
1.0 PROJECT DESCRIPTION
1.1 Site Location & Existing Conditions
The 10.67-acre subject property, located at 3367 South Broadway in Saratoga Springs, Saratoga County,
New York, is identified further as Section 178, Block 2, Lot 15. The property, which was previously a
golf driving range, is vacant and grass covered.
1.2 Site Geology
According to the University of the State of New York, The State Education Department Surficial
Geologic Map of New York, Hudson - Mohawk Sheet (1987), the site is underlain by lacustrine sand. The
University of the State of New York, The State Education Department Geologic Map of New York,
Hudson - Mohawk Sheet (1970) indicates that the subject site is underlain, at depth, by the Middle
Ordovician-age Canajoharie Shale, consisting of black shale, part of Lorraine, Trenton, and Black River
Groups.
WL Enterprises Acquisitions, LLC
Preliminary Geotechnical Investigation
3367 South Broadway
Saratoga Springs, New York
January 9, 2024
Page 2
Environmenta l & Geotechnical Engineers & Consultant s
1.3 Proposed Construction
Based on an October 6, 2022 Preliminary Architectural Site Plan prepared by Bergmeyer of Boston,
Massachusetts, the proposed development includes the construction of a brewery/restaurant with patios
with a footprint of approximately 40,000 square feet within the western portion of the site, with
associated asphalt paved parking and landscaped areas. The proposed building will be a single-story,
wood and steel-framed structure with no basement or crawl space. Whitestone anticipates that the site
will be developed close to site grades to match the nearby roadway. Stormwater management areas are
planned. No new retaining walls are shown on the site plan.
Detailed structural information was not available at the time of this report. Maximum design loads are
assumed to be less than the following: column loads - 120 kips, wall loads - 3.0 kips/lineal foot, and floor
loads - 150 pounds per square foot.
2.0 FIELD EXPLORATION
2.1 Field Exploration
Field exploration at the project site consisted of advancing five borings (identified as B-1 through B-5)
within the proposed building footprint. The borings subsequently were backfilled to the surface with
excavated soils from the investigation. The locations of the borings are shown on the accompanying Test
Location Plan included as Figure 1. Records of Subsurface Exploration are provided in Appendix A.
Field exploration also consisted of advancing eight test pits (identified as TP-1 through TP-8) throughout
the site. The test pits subsequently were backfilled to the surface with excavated soils. The locations of
the test pits are shown on the accompanying Test Location Plan included as Figure 1. Records of
Subsurface Exploration are provided in Appendix A.
Because of the very loose lacustrine sand encountered in the borings, Whitestone contracted Summit
Geoengineering Services to advance two CPT probes (CPT-1 and CPT-2) at the site and then analyze the
CPT data. CPT probes were advanced to effective refusal, presumably on dense glacial till, at depths of
43.9 feet below ground surface (fbgs) and 43.2 fbgs. A Whitestone field representative coordinated CPT
probe locations and observed the advancing of the CPT probes. Whitestone also reviewed the Summit
CPT data related to Site Class and liquefaction potential. The locations of the CPT probes are shown on
the accompanying Test Location Plan included as Figure 1. The Summit CPT Data Report is included in
Appendix A.
The subsurface tests were conducted in the presence of a Whitestone engineer, who performed field tests,
recorded visual classifications, and collected samples of the various strata encountered. Test locations
were established in the field using phone-based GPS. These locations are presumed to be approximate (±
20 feet).
Borings and Standard Penetration Tests (SPTs) were conducted in general accordance with ASTM
International (ASTM) designation D1586. The SPT resistance value (N) can be used as an indicator of
the consistency of fine-grained soils and the relative density of coarse-grained soils. The N-value for
various soil types can be correlated with the engineering behavior of earthworks and foundations.
WL Enterprises Acquisitions, LLC
Preliminary Geotechnical Investigation
3367 South Broadway
Saratoga Springs, New York
January 9, 2024
Page 3
Environmenta l & Geotechnical Engineers & Consultant s
Groundwater level observations, where encountered, were recorded during and immediately after the
completion of field operations prior to backfilling the tests. Seasonal variations, temperature effects,
man-made effects, and recent rainfall conditions may influence the levels of the groundwater, and the
observed levels will depend on the permeability of the soils. Groundwater elevations derived from
sources other than seasonally observed groundwater monitor wells may not be representative of true
groundwater levels.
2.2 Infiltration Testing
Subsurface soil conditions were initially explored by advancing test pits TP-1 through TP-8.
Subsequently, infiltration tests, I-1 through I-8, were performed as falling head tests in cased holes in
general accordance with the procedures in the NYS Stormwater Management Design Manual within the
proposed SWM areas, as shown on Figure 1 Test Location Plan. PVC casing, four inches in diameter,
was installed at the depths shown below. The soil was pre-soaked for approximately one hour.
Following testing, the casings were removed. The results are tabulated below.
SUMMARY OF INFILTRATION TESTING
Location Approximate Ground
Elevation (ft NAVD) Test Depth (fbgs) Approximate Test
Elevation (ft NAVD) Infiltration Rate (in/hr)
I-1 (TP-1) 305 7.3 297.7 >15
I-2 (TP-2) 305 3.7 301.3 >15
I-3 (TP-3) 305 5.0 300 >15
I-4 (TP-4) 305 4.6 300.4 >15
I-5 (TP-5) 305 8.7 296.3 >15
I-6 (TP-6) 305 7.2 297.8 >15
I-7 (TP-7) 305 6.7 298.3 >15
I-8 (TP-8) 305 6.5 298.5 >15
The infiltration testing was conducted within the lacustrine sand which has a low fines content.
Typically, a Factor of Safety (FoS) is applied to measured infiltration rates to account for siltation and
consolidation of soil below the systems over time. Safety factors used should consider how critical the
systems are to the development and the available storage. If the system is critical or storage limited, a
higher FoS should be applied. Infiltration rates are variable and dependent on test depth and stratification.
Whitestone recommends that the unfactored infiltration rate not exceed eight inches per hour and that a
FoS of at least 2.5 be applied to the rate for design purposes.
2.3 Laboratory Testing
Laboratory testing was conducted to determine additional, pertinent engineering characteristics of
representative samples of on-site soils. The laboratory testing was conducted in general accordance with
applicable ASTM standard test methods and included physical/textural testing of representative samples.
The results of the laboratory testing are presented in this section in a general manner and qualitatively
interpreted. The results are incorporated into the findings and recommendations discussed throughout this
report. Quantitative test results are provided in Appendix B.
WL Enterprises Acquisitions, LLC
Preliminary Geotechnical Investigation
3367 South Broadway
Saratoga Springs, New York
January 9, 2024
Page 4
Environmenta l & Geotechnical Engineers & Consultant s
Physical and Textural Analysis: Two representative samples were subjected to a laboratory testing
program that included moisture content determinations (ASTM D2216) and washed gradation analyses
(ASTM D422) in order to conduct supplementary engineering soil classifications in general accordance
with ASTM D2487. The soil stratum tested was classified by the Unified Soil Classification System
(USCS), provided in Appendix C. The results of the laboratory testing are summarized in the following
table.
PHYSICAL/TEXTURAL ANALYSES SUMMARY
Boring Sample Depth (fbgs) Moisture Content
(%)
Passing No. 200
Sieve (%)
USCS
Classification
B-1 S-3 4.0 - 6.0 14.6 6.0 SP-SM
B-4 S-2 2.0 - 4.0 12.4 7.0 SP-SM
3.0 SUBSURFACE CONDITIONS
The subsurface soil conditions encountered within the subsurface tests conducted by Whitestone consisted
of the following generalized strata in order of increasing depth. Records of Subsurface Exploration are
provided in Appendix A.
Surface Cover Materials: The explorations encountered three inches to 12 inches of topsoil at the
ground surface, underlain by 12 inches to 27 inches of subsoil with roots.
Existing Fill: The explorations did not encounter existing fill. However, existing fill may be
encountered during construction between the widely spaced explorations. In addition, sites such as this
may have stump or burn pits from initial clearing, and other buried features.
Lacustrine Sand: Beneath the surface cover materials, the explorations encountered lacustrine sand,
consisting of brown, very loose to loose (occasionally medium dense), poorly graded sand with silt
(USCS: SP-SM). SPT N-values within the lacustrine sand were variable, ranging from one blow per foot
(bpf) to 24 bpf. Borings B-2 and B-3 terminated in this stratum at a depth of 22 fbgs. The test pits
terminated in the lacustrine sand at depths of five fbgs to nine fbgs.
Glacial Till: Beneath the lacustrine sand, borings B-1, B-4, and B-5 encountered glacial till, consisting of
brown, dense, silty sand with gravel (USCS: SM). Borings B-1, B-4, and B-5 terminated in this stratum
at depths of 15.7 fbgs to 22 fbgs.
Groundwater: Groundwater was encountered in the explorations during the investigation at depths of
4.5 fbgs to 7.7 fbgs, but typically five fbgs to six fbgs. Test pits TP-3 and TP-4 caved at a depth of 5.0
fbgs, indicating the likely presence of groundwater at that depth. Groundwater was measured at depths of
3.0 fbgs to 4.0 fbgs while advancing the CPT probes. Groundwater levels should be expected to fluctuate
seasonally and following periods of precipitation.
WL Enterprises Acquisitions, LLC
Preliminary Geotechnical Investigation
3367 South Broadway
Saratoga Springs, New York
January 9, 2024
Page 5
Environmenta l & Geotechnical Engineers & Consultant s
4.0 CONCLUSIONS & RECOMMENDATIONS
The CPT probes determined that the natural sands below the groundwater table are generally not
susceptible to seismic liquefaction. However, thorough surface compaction is recommended due to the
loose sands, as discussed below.
Contingent upon construction phase evaluation, Whitestone’s findings indicate that the proposed
structures may be supported on conventional shallow foundations bearing on a layer of crushed stone
encapsulated in geotextile separation fabric placed over the approved lacustrine sand and/or structural fill
placed on the lacustrine sand. The borings did not encounter existing fill. However, existing fill may be
encountered between the widely spaced borings. Any existing fill encountered beneath the underside of
footing level should be overexcavated and replaced with structural fill. Ground-supported floor slabs may
derive support from the inspected, improved, and approved lacustrine sand and/or controlled structural fill
materials. Additionally, the site conditions support the use of typical pavement sections using standard
New York State Department of Transportation (NYSDOT) specified materials.
The following recommendations have been developed on the basis of the previously described project
characteristics and subsurface conditions encountered within the limited exploration performed. If there
are any significant changes to the project characteristics or if significantly different subsurface conditions
are encountered during construction, Whitestone should be consulted, so that the recommendations of this
report can be reviewed.
4.1 Site Preparation & Earthwork
Surface Cover Stripping: Prior to stripping operations, any utilities should be identified and secured.
Topsoil, organic subsoil, vegetation, trees, shrubs, and other organic matter should be removed from
within and at least five feet beyond the limits of the proposed building footprint and other site structures,
as well as any other area that will require controlled structural fill placement. Tree/shrub removal should
include the removal of stumps and root material. Root structures will require removal in excess of the
few inches of topsoil encountered at the ground surface. Any existing concrete or masonry structural
elements encountered during excavation should be removed entirely. The contractor should be required
to conduct earthwork in accordance with the recommendations in this report, including backfilling any
excavation, etc. with structural fill. Fill or backfill placed within the proposed building area should be
placed as structural fill in accordance with the recommendations of this report.
Surface Preparation/Proofrolling: Prior to placing any fill to raise or restore grades to the desired
subgrade elevations, if required, the existing exposed soils should be compacted to a firm and unyielding
surface with several passes in two perpendicular directions of a minimum 10-ton vibratory compactor.
The surface should then be proofrolled with a loaded tandem axle truck in the presence of the
geotechnical engineer to help identify soft or loose pockets that may require removal and replacement, or
further evaluation. Proofrolling should be performed after a suitable period of dry weather to reduce the
likelihood of degrading an otherwise stable subgrade. Should construction be attempted in the winter or
when temperatures are below freezing, Whitestone should be contracted for alternative surface
preparation recommendations. Fill and backfill should be placed and compacted in accordance with
Section 4.2.
Weather Performance Criteria: The lacustrine sand is typically well drained. Achieving compaction
and maintaining surface compaction during dry weather may be difficult. The lacustrine sand deposit
may need to be wetted on a regular basis to achieve compaction and will be easily disturbed at the surface
by construction activities. Routine grading, wetting of soil, and proofrolling will likely be required to
maintain exposed subgrades.
WL Enterprises Acquisitions, LLC
Preliminary Geotechnical Investigation
3367 South Broadway
Saratoga Springs, New York
January 9, 2024
Page 6
Environmenta l & Geotechnical Engineers & Consultant s
Subgrade Protection and Inspection: Every effort should be made to reduce disturbance of the on-site
soils by construction traffic and surface runoff. The on-site materials may deteriorate when subjected to
repeated construction traffic and/or inclement weather, which would require removal and replacement.
The contractor should be responsible for protection of subgrades and minimization of exposure of the site
materials to precipitation by covering stockpiles and subgrades with plastic and preventing ponding of
water by sealing subgrades before precipitation events and grading the site to allow proper drainage of
surface water. All rutting from construction equipment should be removed prior to any forecasted or
actual precipitation. Whitestone should be retained to observe soil conditions during construction and
review the suitability of prepared foundation subgrades for support of design loads.
Groundwater Control: Groundwater was encountered in the explorations during the initial investigation
at depths of 4.5 fbgs to 7.7 fbgs, but typically 5.0 fbgs to 6.0 fbgs. However, while advancing the CPT
probes, groundwater was measured at depths of 3.0 fbgs to 4.0 fbgs. Shallower groundwater may be
encountered during construction, perched above impermeable layers. As such, construction phase
dewatering may consist of temporarily lowering the groundwater table, and removing surface water
runoff, infiltrating water, or trapped water. Whitestone anticipates that construction phase dewatering
could include installing temporary sump pits and filtered pumps within trenches and excavations.
Whitestone recommends that foundation construction occur during periods of relatively dry weather.
Every effort should be made to maintain drainage of surface water runoff away from construction areas
by grading and limiting the exposure of foundation areas to precipitation.
Because of the shallow groundwater, Whitestone recommends a minimum four-inch diameter perforated
PVC or HDPE perimeter drain be incorporated into the foundation design. The perimeter drain should be
installed close to the bottom of the footings, encased in minus 0.75-inch crushed stone wrapped in
geotextile separation fabric. The groundwater collected by the foundation drain should flow to nearby
detention ponds or other stormwater management system. Provided the perimeter drain is installed and
the soil beneath the slab is prepared in accordance with the recommendations in this report, additional
sub-slab drains will not be required.
4.2 Structural Fill & Backfill
Imported Fill Material: Any imported material placed as structural fill or backfill to restore design
grades should consist of clean, relatively well-graded sand or gravel with a maximum particle size of
three inches and up to 15 percent of material finer than a #200 sieve. The material should be free of clay
lumps, organics, and deleterious material. Any imported structural fill material should be approved by a
qualified geotechnical engineer prior to delivery to the site.
Soil Reuse: Whitestone anticipates that the lacustrine sand will be suitable for selective reuse as
structural fill/backfill material, provided that soil moisture contents are controlled within three percent of
optimum moisture level, any particles larger than three inches in diameter are either removed or crushed,
and any deleterious material is segregated. Reuse of the site soils will be contingent on careful review in
the field by the owner’s geotechnical engineer by visual observation during construction as recommended
herein.
Compaction and Placement Requirements: Fill and backfill should be placed in loose lifts no more
than 12 inches thick when compacted with a vibratory roller compactor weighing at least one ton, and
eight inches when compacted with a plate compactor. Fill and backfill should be compacted to 95 percent
of the maximum dry density within three percent of the optimum moisture content, as determined by
ASTM D1557 (Modified Proctor).
WL Enterprises Acquisitions, LLC
Preliminary Geotechnical Investigation
3367 South Broadway
Saratoga Springs, New York
January 9, 2024
Page 7
Environmenta l & Geotechnical Engineers & Consultant s
4.3 Foundation Design Criteria
Foundations: Contingent upon construction phase evaluation and thorough surface compaction,
Whitestone preliminarily recommends supporting the proposed structures on conventional shallow spread
foundations designed to bear on a minimum eight-inch thick layer of minus 0.75-inch crushed stone
encapsulated in geotextile separation fabric (Mirafi 140N, or similar) placed over the approved lacustrine
sand and/or over controlled structural fill materials that are properly placed and compacted as described
herein. The borings did not encounter existing fill. However, existing fill may be encountered between
the widely spaced borings. Any existing fill encountered beneath the underside of footing level should be
overexcavated and replaced with structural fill. Foundations bearing within these materials may be
designed using a maximum net allowable bearing pressure of 4,000 pounds per square foot, provided
footing subgrades are thoroughly compacted with a full-sized vibratory roller or a walk-behind, double-
drum, vibratory roller.
The geotechnical engineer should review foundation subgrades, which should be compacted in the
presence of the geotechnical engineer to densify loose upper soils and disturbed soils. Regardless of
loading conditions, new foundations should be sized no less than minimum dimensions of 24 inches for
continuous wall footings and 36 inches for isolated column footings. A minimum four-inch diameter
perforated perimeter drain should be incorporated into the foundation design.
The lacustrine sand is easily disturbed by construction activities. The recommended layer of crushed
stone encapsulated in geotextile separation fabric will reduce the likelihood of disturbance and provide a
working surface for formwork and reinforcing steel placement.
Footings subject to lateral loads and/or overturning should be designed so that the maximum toe pressure
due to the combined effect of vertical loads and overturning moment do es not exceed the recommended
maximum allowable net bearing pressure. In addition, positive contact pressure should be maintained
throughout the base of the footings such that no uplift or tension exists between the base of the footings
and the supporting soil. Uplift loads should be resisted by the weight of the concrete. Side fri ction
should be neglected when proportioning the footings so that lateral resistance should be provided by
friction resistance at the base of the footings. An allowable coefficient of friction against sliding of 0.4 is
recommended for use in the design of the foundations bearing within the existing site soils or imported
structural fill soils.
Seismic Site Class: Based on a review of the subsurface conditions relevant to the New York State
Building Code, the subject site has been assigned a Site Class D. The shear wave velocities measured by
the CPT probes (average 750 feet per second for the sand unit to a depth of 40 fbgs) per ASTM D7400
confirm Site Class D.
Whitestone also considers the site soils to generally have an adequate Factor of Safety against earthquake
induced liquefaction, provided the ground surface and footing subgrades are thoroughly compacted, as
discussed above. Limited thin layers of very loose sand at depth are unlikely to cause loss of bearing in
the event of a major earthquake. This Whitestone assessment concurs with the Summit analysis of the
site data, which is attached.
Inspection/Overexcavation Criteria: Whitestone recommends that the suitability of the bearing soils at
the footing bottoms be reviewed by a geotechnical engineer immediately prior to placing concrete for the
footings. In the event that areas of unsuitable materials are encountered, additional overexcavation and
replacement of the materials may be necessary to provide a suitable footing subgrade. Any
overexcavation to be restored with structural fill should extend at least one foot laterally beyond footing
edges for each vertical foot of overexcavation. Lateral overexcavation may be eliminated if grades are
restored with lean concrete.
WL Enterprises Acquisitions, LLC
Preliminary Geotechnical Investigation
3367 South Broadway
Saratoga Springs, New York
January 9, 2024
Page 8
Environmenta l & Geotechnical Engineers & Consultant s
Frost Coverage: Foundations subject to frost action should be placed at least 48 inches below adjacent
exterior grades, or the depth required by local building codes, to provide protection from frost penetration.
Interior foundations not subject to frost action (including during construction) may be placed at a
minimum depth of 18 inches below the floor slab subgrade.
Settlement: Whitestone estimates post construction settlements of proposed foundations of less than one
inch, if the recommendations outlined in this report are properly implemented. Differential settlement of
foundations should be less than one half inch. Although CPT data indicates the site is susceptible to
liquefaction in the event of an earthquake the existing loose sands may consolidate resulting in
settlements greater than one inch following a significant seismic event.
4.4 Floor Slab
Whitestone anticipates that the properly inspected, approved, and improved lacustrine sand, and/or
compacted structural fill will be suitable for support of the proposed floor slab provided these materials
are properly evaluated, compacted, and proofrolled in accordance with the recommendations of this report
during favorable weather conditions. Areas that are, or become, softened or disturbed as a result of
wetting and/or repeated exposure to construction traffic or contain objectionable materials should be
removed and replaced with compacted structural fill. The properly prepared on-site soils are expected to
yield a minimum subgrade modulus (k) of 150 psi/in.
A minimum 12-inch layer of NYSDOT 733-04 Subbase Course, Type 2 (or approved equivalent) should
be placed below the floor slab to provide a uniform granular base. If the floor supports moisture-sensitive
covering or equipment, a moisture vapor barrier should also be installed beneath the floor slab in
accordance with flooring manufacturer’s recommendations.
4.5 Pavement Design Criteria
Whitestone anticipates that the properly inspected, approved, and improved lacustrine sand, and/or
compacted structural fill/backfill placed to raise or restore design elevations will be suitable for support of
the proposed pavements, provided these materials are properly evaluated, compacted, and proofrolled in
accordance with the recommendations of this report during favorable weather conditions.
A California Bearing Ratio value of 8.0 has been assigned to the properly prepared subgrade soils for
pavement design purposes. This value was correlated with pertinent soil support values and assumed
traffic loads to prepare flexible and rigid pavement designs per the AASHTO Guide for the Design of
Pavement Structures.
Design traffic loads were assumed based on typical volumes for similar facilities and correlated with 18-
kip equivalent single axle loads (ESAL) for a 20-year life. Estimated maximum pavement loads of
30,000 ESALs and 75,000 ESALs were used for the standard-duty and heavy-duty pavement areas,
respectively. These values assume the pavements primarily will accommodate both automobile and
limited heavier truck traffic, with the heavier truck traffic designated to the main drive lanes. Actual
loading experienced is anticipated to be less than these values.
Pavement components should meet material specifications from NYSDOT Standard Specifications
specified below. The recommended flexible pavement sections are tabulated below:
WL Enterprises Acquisitions, LLC
Preliminary Geotechnical Investigation
3367 South Broadway
Saratoga Springs, New York
January 9, 2024
Page 9
Environmenta l & Geotechnical Engineers & Consultant s
FLEXIBLE PAVEMENT SECTION
Layer Material
Standard-Duty
Thickness
(inches)
Heavy-Duty
Thickness
(inches)
Asphalt Top Course NYSDOT 12.5 mm F3 Top Course HMA, 70
Series Compaction (Superpave); PG64S-22 1.5 1.5
Asphalt Binder Course NYSDOT 19 mm F9 Binder Course HMA, 70
Series Compaction (Superpave); PG64S-22 1.5 2.5
Granular Subbase NYSDOT 733-04 Type 2 Subbase 12.0 12.0
A rigid concrete pavement should be used to provide suitable support at areas of high traffic or severe
turns, such as at the trash enclosure, service access lanes, and ingress/egress locations. The recommended
rigid pavement is tabulated below:
RIGID PAVEMENT SECTION
Layer Material Thickness (inches)
Surface 4,000 psi air-entrained concrete 6.0 1
Granular Subbase NYSDOT 733-04 Type 2 Subbase 12.0
1 The outer edges of concrete pavements are susceptible to damage as trucks move from rigid pavement to adjacent flexible
pavement. Therefore, the thickness at the outer two feet of the rigid concrete pavement should be 12 inches.
The pavement section thickness designs presented in this report are based on the design parameters
detailed herein and are contingent on proper construction, inspection, and maintenance. Additional
pavement thickness may be required by local code. The designs are contingent on achieving the
minimum soil support value in the field. To accomplish this requirement, subgrade soil and supporting
fill or backfill must be placed, compacted, and evaluated in accordance with the recommendations of this
report. Proper drainage should be provided for the pavement structure, including appropriate grading and
surface water control.
The performance of the pavement also will depend on the quality of materials and workmanship.
Whitestone recommends that NYSDOT standards for materials, workmanship, and maintenance be
applied to this site. Project specifications should include verifying that the installed asphaltic concrete
material composition is within tolerance for the specified materials and that the percentage of air voids of
the installed pavement is within specified ranges for the respective materials. Rigid concrete pavements
should be suitably air-entrained, jointed, and reinforced in general accordance with ACI 330R-08 Guide
for the Design and Construction of Concrete Parking Lots.
4.6 Retaining Walls/Lateral Earth Pressures
The following parameters may be used for design of retaining walls, such as at loading docks, any below-
grade walls, and other structures reliant on granular materials to provide adequate drainage. However, the
parameters are not directly applicable to the design of mechanically stabilize d earth (MSE) retaining
walls, which require proprietary design methods for the selected earth retention system.
WL Enterprises Acquisitions, LLC
Preliminary Geotechnical Investigation
3367 South Broadway
Saratoga Springs, New York
January 9, 2024
Page 10
Environmenta l & Geotechnical Engineers & Consultant s
Retaining/below-grade walls should be capable of withstanding active and at-rest earth pressures.
Backfill soils adjacent to these structures should consist of freely draining granular fill composed
primarily of coarse to fine sand. With an active earth pressure coefficient (Ka) of 0.33, level backfill, and
an assumed maximum backfill soil unit weight of 140 pounds per cubic foot (pcf), an equ ivalent fluid
pressure of 46 psf per foot of wall height should be used in design of retaining/below-grade walls which
are free to rotate.
Retaining/below-grade walls and wall corners typically are restrained from lateral movement and should
be designed using at-rest earth pressures. A coefficient of at-rest earth pressure (Ko) of 0.5, for a level
backfill, is recommended for retaining/below-grade walls designed to resist at-rest earth pressures, which
assume no lateral movement. With an assumed maximum total unit weight of backfill of approximately
140 pcf, an equivalent fluid pressure of 70 pounds per square foot per foot of wall height should be used
in design of restrained retaining/below-grade wall and wall corners. A coefficient of friction of 0.4
against sliding can be used for concrete on the existing site soils. Additional lateral earth pressures from a
sloped backfill or any temporary or long-term surcharge loads also should be included in the design.
Retaining wall design should include a global stability analysis.
Whitestone recommends that granular soils be used to backfill behind retaining walls. The granular
backfill materials should consist of clean, relatively well graded sand or gravel with a maximum particle
size of three inches and up to 15 percent of material finer than a #200 U.S. Standard sieve. Whitestone
recommends that backfill directly behind any walls be compacted with light, hand-held compactors.
Heavy compactors and grading equipment should not be allowed to operate within a zone of influence
measured at a 45-degree angle from the base of the walls during backfilling to avoid developing excessive
temporary or long-term lateral soil pressures.
Positive drainage should be provided at the base of the below-grade walls. Where wall drainage is not
provided or cannot be relied upon, walls are designed to withstand full hydrostatic pressure.
Whitestone should be notified if any other retaining structures or design considerations requiring lateral
earth pressure estimations are proposed. Specific recommendations for temporary retaining structures are
beyond Whitestone’s scope of work.
4.7 Excavations
The site soils encountered during the investigation generally are most consistent with, at least, Type C
Soil Conditions as defined by 29 CFR Part 1926 (OSHA) that require a maximum unbraced excavation
angle of 1.5:1 (horizontal:vertical). Actual conditions encountered during construction should be
evaluated by a competent person (as defined by OSHA), so that safe excavation methods and/or shoring
and bracing requirements are implemented.
5.0 SUPPLEMENTAL POST INVESTIGATION SERVICES
Construction Inspection and Monitoring: The owner’s geotechnical engineer with specific knowledge
of the site subsurface conditions and design intent should conduct inspection, testing, and consultation
during construction as described in previous sections of this report. Monitoring and testing should also be
performed to confirm that any encountered underground structures are properly backfilled, the existing
surface cover materials are properly removed, and suitable materials, used for controlled fill, are properly
placed and compacted over suitable subgrade soils. The proofrolling of all subgrades prior to building,
floor slab, and pavement support should be witnessed and documented by the owner’s geotechnical
engineer.
WL Enterprises Acquisitions, LLC
Preliminary Geotechnical Investigation
3367 South Broadway
Saratoga Springs, New York
January 9, 2024
Page 11
Environmenta l & Geotechnical Engineers & Consultant s
6.0 CLOSING
Whitestone’s geotechnical division appreciates the opportunity to be of service to WL Enterprises
Acquisitions, LLC. Whitestone has the capability to conduct the additional geotechnical engineering
services recommended herein. Please contact us at (585) 252-6879 with any questions regarding this
report.
Sincerely,
WHITESTONE
Richard W.M. McLaren, P.E. Ryan R. Roy, P.E.
Senior Consultant Vice President
RWM/th N:\Job Folders\2023\2321159GM\Reports and Submittals\WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 ROGI 1-9-24.doc
Enclosures
FIGURE 1
Test Location Plan
B-1B-2B-3B-4B-5TP-1I-ITP-2I-2TP-3I-3TP-5I-5TP-6I-6TP-7I-7TP-4I-4TP-8I-8CPT-1CPT-2FIGURE:DATE:PROJECT #:SCALE:CLIENT:DESIGNED BY:PROJ. MGR.:PROJECT:
DRAWING TITLE:LEGEND BORING LOCATIONREFERENCESUBJECT PROPERTY BOUNDARYB-116 OLD FORGE ROAD, SUITE A, ROCKY HILL, CT 06067
860.726.7889 WHITESTONEASSOC.COMTHIS PLAN IS BASED ON A 10/6/22 PRELIMINARY ARCHITECTURALSITE PLAN, PREPARED BY BERGMEYER.1" = 80'12/21/231RRMRGM2321159.Y00TEST LOCATION PLAN
WL ENTERPRISES ACQUISITIONS, LLC
c/o SNYDER, KILEY, TOOHEY, CORBETT & COX, LLP
PRELIMINARY GEOTECHNICAL INVESTIGATION &
STORMWATER MANAGEMENT AREA EVALUATION
3376 SOUTH BROADWAY
TAX MAP NO.: 178.-2-15
SARATOGA SPRINGS, SARATOGA COUNTY, NEW YORKNOTE: ALL LOCATIONS ARE APPROXIMATE.WHITESTONE TEST PIT LOCATIONTP-1 INFILTRATION TESTI-1CPT-1CONE PENETRATION TEST
APPENDIX A
Records of Subsurface Exploration
1 1
Project:
Location:
Surface Elevation:±||
Termination Depth:Date Completed:||
Proposed Location:|299.0
At Completion:|-- --|
|--24 Hours: --|
No Type
0.0
5.0
10.0
15.0
16.0
20.0
25.0
GLACIAL
LACUSTRINE
SAND
20 - 20.7 S-8 51 -40/2"7 -
10 - 12 S-6 16 6
2016-40/
5"
As Above, Medium Dense (SP-SM)
Brown, Dense, Silty Sand with Gravel (SM)
0 - 2 S-1
3 1
--
---2 - 4
WOH
/12"
2
1
As Above, Very Dense
Boring B-1 Terminated at a Depth of 20.7 Feet Below Ground Surface.
TILL
TS 6" Topsoil
18" Subsoil, Roots
Brown, Very Loose, Poorly Graded Sand with Silt (SP-SM)
SUBSOIL
-- --
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKSDepth
(feet)Blows Per 6"
Rec.
(in.)N (feet)(Classification)
Equipment:Geoprobe 7822DT 24 Hours:
--Drill / Test Method:HSA / SPT (Autohammer)Contractor:CC --
Building Logged By:OR During:6.0
At Completion:
(ft NAVD88)
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
305.0 feet Above NAVD88 Date Started:11/8/2023 Water Depth Elevation Cave-In Depth
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
RECORD OF Boring No.: B-1
SUBSURFACE EXPLORATION Page of
Elevation
20.7 feet bgs 11/8/2023 (feet bgs)(ft NAVD88)(feet bgs)
As Above, Loose (SP-SM)
As Above, Very Loose to Loose (SP-SM)
As Above, Loose (SP-SM)
As Above (SP-SM)
-
5
2415 - 17 S-7
10 -4
6 -8 -
2 --
---
-
4 - 6
6 - 8
8 - 10 S-5
S-4
S-3
S-2
---
3
1 17 2
3 -
2 28
7
4
3 4 3
2 1 3 2
3 3 2 2
3
15
20
18
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Boring Logs 11-8-23 12/22/2023
1 1
Project:
Location:
Surface Elevation:±||
Termination Depth:Date Completed:||
Proposed Location:|299.0
At Completion:|-- --|
|--24 Hours: --|
No Type
0.0
5.0
10.0
15.0
20.0
25.0
20 - 22 S-6 2 3 8 9 12 11
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
RECORD OF Boring No.: B-2
SUBSURFACE EXPLORATION Page of
Elevation
22.0 feet bgs 11/8/2023 (feet bgs)(ft NAVD88)(feet bgs)(ft NAVD88)
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
305.0 feet Above NAVD88 Date Started:11/8/2023 Water Depth Elevation Cave-In Depth
Drill / Test Method:HSA / SPT (Autohammer)Contractor:CC --At Completion: --
Building Logged By:OR During:6.0
--Equipment:Geoprobe 7822DT 24 Hours: --
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKSDepth
(feet)Blows Per 6"
Rec.
(in.)N (feet)(Classification)
0 - 2 S-1 11 10 19 1928
TS 12" Topsoil
2 - 4 S-2 3 3 4 5 13 7 Brown, Loose, Poorly Graded Sand with Silt (SP-SM)
3 2
SUBSOIL 18" Subsoil, Roots
8 - 10 S-4 1
45 - 7 S-3 3
As Above, Very Loose (SP-SM)1 22 1
15 - 17 S-5 1 1 16 2
As Above, Medium Dense (SP-SM)
Boring B-2 Terminated at a Depth of 22.0 Feet Below Ground Surface.
LACUSTRINE
As Above (SP-SM)17 5
1/12"
1 1
SAND
As Above (SP-SM)
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Boring Logs 11-8-23 12/22/2023
1 1
Project:
Location:
Surface Elevation:±||
Termination Depth:Date Completed:||
Proposed Location:|299.0
At Completion:|-- --|
|--24 Hours: --|
No Type
0.0
5.0
10.0
15.0
20.0
25.0
SAND
20 - 22 S-6 7 8 16 21 15 24
8 2 16 22
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
RECORD OF Boring No.: B-3
SUBSURFACE EXPLORATION Page of
Elevation
22.0 feet bgs 11/8/2023 (feet bgs)(ft NAVD88)(feet bgs)(ft NAVD88)
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
305.0 feet Above NAVD88 Date Started:11/8/2023 Water Depth Elevation Cave-In Depth
Drill / Test Method:HSA / SPT (Autohammer)Contractor:CC --At Completion: --
Building Logged By:OR During:6.0
--Equipment:Geoprobe 7822DT 24 Hours: --
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKSDepth
(feet)Blows Per 6"
Rec.
(in.)N (feet)(Classification)
0 - 2 S-1 2 2
SUBSOIL 21" Subsoil, Roots
3 2 24 5
TS 9" Topsoil
2 17 32 - 4 S-2 2 2 1 Brown, Very Loose, Poorly Graded Sand with Silt (SP-SM)
3 As Above (SP-SM)5 - 7 S-3 2 2 1 2 16
8 - 10 S-4 2 2 24 4 As Above, Very Loose to Loose (SP-SM)
LACUSTRINE
15 - 17 S-5 4 14 As Above, Medium Dense (SP-SM)
As Above (SP-SM)
Boring B-3 Terminated at a Depth of 22.0 Feet Below Ground Surface.
2 2
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Boring Logs 11-8-23 12/22/2023
1 1
Project:
Location:
Surface Elevation:±||
Termination Depth:Date Completed:||
Proposed Location:|299.5
At Completion:|-- --|
|--24 Hours: --|
No Type
0.0
5.0
10.0
15.0
20.0
21.0
25.0
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
RECORD OF Boring No.: B-4
SUBSURFACE EXPLORATION Page of
Elevation
22.0 feet bgs 11/8/2023 (feet bgs)(ft NAVD88)(feet bgs)(ft NAVD88)
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
305.0 feet Above NAVD88 Date Started:11/8/2023 Water Depth Elevation Cave-In Depth
Drill / Test Method:HSA / SPT (Autohammer)Contractor:CC --At Completion: --
Building Logged By:OR During:5.5
--Equipment:Geoprobe 7822DT 24 Hours: --
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKSDepth
(feet)Blows Per 6"
Rec.
(in.)N (feet)(Classification)
0 - 2 S-1 1 2 2 2 15 4
TS 9" Topsoil
2 10 52 - 4 S-2 2 3 2 Brown, Loose, Poorly Graded Sand with Silt (SP-SM)
6 As Above (SP-SM)5 - 7 S-3 3 3 3 3 16
8 - 10 S-4 3 1 2 1 14
10 - 12 S-5 1 1
3 As Above, Very Loose (SP-SM)
SAND
LACUSTRINE As Above (SP-SM)16 1
15 - 17 S-5 6 11 8 7 18 19 As Above, Medium Dense (SP-SM)
20 - 22 S-6 7 9 29 44 12 38 As Above (SP-SM)
GLACIAL Brown, Very Dense, Silty Sand with Gravel (SM)
TILL
Boring B-4 Terminated at a Depth of 22.0 Feet Below Ground Surface.
SUBSOIL 15" Subsoil, Roots
1/12"
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Boring Logs 11-8-23 12/22/2023
1 1
Project:
Location:
Surface Elevation:±||
Termination Depth:Date Completed:||
Proposed Location:|300.0
At Completion:|-- --|
|--24 Hours: --|
No Type
0.0
5.0
10.0
15.0
15 - 15.7 S-5 16 -0 -
20.0
25.0
LACUSTRINE
SAND
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
Cave-In Depth
Drill / Test Method:HSA / SPT (Autohammer)Contractor:CC --At Completion: --
Building Logged By:OR During:5.0
RECORD OF Boring No.: B-5
SUBSURFACE EXPLORATION Page of
Elevation
15.7 feet bgs 11/8/2023 (feet bgs)(ft NAVD88)(feet bgs)(ft NAVD88)
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
305.0 feet Above NAVD88 Date Started:11/8/2023 Water Depth Elevation
--Equipment:Geoprobe 7822DT 24 Hours: --
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKSDepth
(feet)Blows Per 6"
Rec.
(in.)N (feet)(Classification)
0 - 2 S-1 2 2
SUBSOIL 12" Subsoil, Roots
3 2 20 5
TS 9" Topsoil
1 18 22 - 4 S-2 2 1 1 Brown, Very Loose, Poorly Graded Sand with Silt (SP-SM)
As Above (SP-SM)5 - 7 S-3 1 1 18 11/12"
8 - 10 S-4 4 1 1 1 14 2 As Above (SP-SM)
40/2"
Boring B-5 Terminated at a Depth of 15.7 Feet Below Ground Surface.
No Recovery
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Boring Logs 11-8-23 12/22/2023
TP-1
of 1
Project:
Location:
Surface Elevation:±305.0 feet NAVD88 ||
Termination Depth:7.5 ||
Proposed Location:Logged By:|--
Contractor:At Completion:|----|
Rig Type:|--
Depth (ft.)Type
0.0
5.0
10.0
15.0
5.5 1 Grab
RECORD OF Test Pit No.:
SUBSURFACE EXPLORATION Page 1
Date Started:11/9/2023 Water Depth Elevation Cave-In Depth Elevation
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
(ft NAVD88)
SWM Area OR During: --
feet bgs Date Completed:11/9/2023 (feet bgs)(ft NAVD88)(feet bgs)
Test Method:Visual Observation Caterpillar 308E 24 Hours: --
Excavating Method:Midi Excavator JD --At Completion:--
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKS
Number (feet)(Classification)
TOPSOIL 9" Topsoil
SUBSOIL 24" Subsoil, Roots
LACUSTRINE Brown, Poorly Graded Sand with Silt (SP-SM)
SAND
Test Pit TP-1 Terminated at Depth of 7.5 Feet Below Ground Surface.
Infiltration Test in Adjacent
Augered Hole @ 7.3 fbgs
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Test Pit Logs 11-9-23 12/22/2023
TP-2
of 1
Project:
Location:
Surface Elevation:±305.0 feet NAVD88 ||
Termination Depth:7.0 ||
Proposed Location:Logged By:|300.0
Contractor:At Completion:|----|
Rig Type:|--
Depth (ft.)Type
0.0
5.0
10.0
15.0
5.5 2 Grab
Test Pit TP-2 Terminated at Depth of 7.0 Feet Below Ground Surface.
LACUSTRINE Brown, Poorly Graded Sand with Silt (SP-SM)
SAND
1 Grab3.5
Infiltration Test in Adjacent
Augered Hole @ 3.7 fbgs
TOPSOIL 12" Topsoil
SUBSOIL 12" Subsoil, Roots
(feet)(Classification)
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKS
Number
Test Method:Visual Observation Caterpillar 308E 24 Hours: --
Excavating Method:Midi Excavator JD --At Completion:--
(ft NAVD88)
SWM Area OR During:5.0
feet bgs Date Completed:11/9/2023 (feet bgs)(ft NAVD88)(feet bgs)
RECORD OF Test Pit No.:
SUBSURFACE EXPLORATION Page 1
Date Started:11/9/2023 Water Depth Elevation Cave-In Depth Elevation
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Test Pit Logs 11-9-23 12/22/2023
TP-3
of 1
Project:
Location:
Surface Elevation:±305.0 feet NAVD88 ||
Termination Depth:5.0 ||
Proposed Location:Logged By:|--
Contractor:At Completion:|--5.0 |
Rig Type:|--
Depth (ft.)Type
0.0
5.0
10.0
15.0
Infiltration Test in Adjacent
Augered Hole @ 5 fbgs
SAND
Test Pit TP-3 Terminated at Depth of 5.0 Feet Below Ground Surface.
SUBSOIL 15" Subsoil, Roots
LACUSTRINE Brown, Poorly Graded Sand with Silt (SP-SM)
TOPSOIL 9" Topsoil
(feet)(Classification)
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKS
Number
Test Method:Visual Observation Caterpillar 308E 24 Hours: --
Excavating Method:Compact Excavator JD --At Completion:300.0
(ft NAVD88)
SWM Area OR During: --
feet bgs Date Completed:11/9/2023 (feet bgs)(ft NAVD88)(feet bgs)
RECORD OF Test Pit No.:
SUBSURFACE EXPLORATION Page 1
Date Started:11/9/2023 Water Depth Elevation Cave-In Depth Elevation
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Test Pit Logs 11-9-23 12/22/2023
TP-4
of 1
Project:
Location:
Surface Elevation:±305.0 feet NAVD88 ||
Termination Depth:5.0 ||
Proposed Location:Logged By:|--
Contractor:At Completion:|--5.0 |
Rig Type:|--
Depth (ft.)Type
0.0
5.0
10.0
15.0
Infiltration Test in Adjacent
Augered Hole @ 4.6 fbgs
SAND
Test Pit TP-4 Terminated at Depth of 5.0 Feet Below Ground Surface.
SUBSOIL 21" Subsoil, Roots
LACUSTRINE Brown, Poorly Graded Sand with Silt (SP-SM)
TOPSOIL 3" Topsoil
(feet)(Classification)
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKS
Number
Test Method:Visual Observation Caterpillar 308E 24 Hours: --
Excavating Method:Compact Excavator JD --At Completion:300.0
(ft NAVD88)
SWM Area OR During: --
feet bgs Date Completed:11/9/2023 (feet bgs)(ft NAVD88)(feet bgs)
RECORD OF Test Pit No.:
SUBSURFACE EXPLORATION Page 1
Date Started:11/9/2023 Water Depth Elevation Cave-In Depth Elevation
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Test Pit Logs 11-9-23 12/22/2023
TP-5
of 1
Project:
Location:
Surface Elevation:±305.0 feet NAVD88 ||
Termination Depth:9.0 ||
Proposed Location:Logged By:|--
Contractor:At Completion:|297.3 --|
Rig Type:|--
Depth (ft.)Type
0.0
5.0
10.0
15.0
7.5 1 Grab
Test Pit TP-5 Terminated at Depth of 9.0 Feet Below Ground Surface.
Infiltration Test in Adjacent
Augered Hole @ 8.7 fbgs
SAND
LACUSTRINE Brown, Poorly Graded Sand with Silt (SP-SM)
SUBSOIL 18" Subsoil, Roots
TOPSOIL 12" Topsoil
(feet)(Classification)
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKS
Number
Test Method:Visual Observation Caterpillar 308E 24 Hours: --
Excavating Method:Compact Excavator JD 7.7 At Completion:--
(ft NAVD88)
SWM Area OR During: --
feet bgs Date Completed:11/9/2023 (feet bgs)(ft NAVD88)(feet bgs)
RECORD OF Test Pit No.:
SUBSURFACE EXPLORATION Page 1
Date Started:11/9/2023 Water Depth Elevation Cave-In Depth Elevation
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Test Pit Logs 11-9-23 12/22/2023
TP-6
of 1
Project:
Location:
Surface Elevation:±305.0 feet NAVD88 ||
Termination Depth:7.5 ||
Proposed Location:Logged By:|299.0
Contractor:At Completion:|299.7 --|
Rig Type:|--
Depth (ft.)Type
0.0
5.0
10.0
15.0
2.5 1 Grab
Augered Hole @ 7.2 fbgs
Test Pit TP-6 Terminated at Depth of 7.5 Feet Below Ground Surface.
Infiltration Test in Adjacent
LACUSTRINE
SAND Brown, Poorly Graded Sand with Silt (SP-SM)
SUBSOIL 12" Subsoil, Roots
TOPSOIL 12" Topsoil
(feet)(Classification)
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKS
Number
Test Method:Visual Observation Caterpillar 308E 24 Hours: --
Excavating Method:Midi Excavator JD 5.3 At Completion:--
(ft NAVD88)
SWM Area OR During:6.0
feet bgs Date Completed:11/9/2023 (feet bgs)(ft NAVD88)(feet bgs)
RECORD OF Test Pit No.:
SUBSURFACE EXPLORATION Page 1
Date Started:11/9/2023 Water Depth Elevation Cave-In Depth Elevation
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Test Pit Logs 11-9-23 12/22/2023
TP-7
of 1
Project:
Location:
Surface Elevation:±305.0 feet NAVD88 ||
Termination Depth:7.0 ||
Proposed Location:Logged By:|300.0
Contractor:At Completion:|300.5
Rig Type:|--
Depth (ft.)Type
0.0
5.0
10.0
15.0
5 1 Grab
Test Pit TP-7 Terminated at Depth of 7.0 Feet Below Ground Surface.
Infiltration Test in Adjacent
Augered Hole @ 6.7 fbgs
LACUSTRINE Brown, Poorly Graded Sand with Silt (SP-SM)
SAND
SUBSOIL 18" Subsoil, Roots
TOPSOIL 6" Topsoil
(feet)(Classification)
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKS
Number
Test Method:Visual Observation Caterpillar 308E 24 Hours: --
Excavating Method:Compact Excavator JD 4.5 At Completion:-- --
(ft NAVD88)
SWM Area OR During:5.0
feet bgs Date Completed:11/9/2023 (feet bgs)(ft NAVD88)(feet bgs)
RECORD OF Test Pit No.:
SUBSURFACE EXPLORATION Page 1
Date Started:11/9/2023 Water Depth Elevation Cave-In Depth Elevation
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Test Pit Logs 11-9-23 12/22/2023
TP-8
of 1
Project:
Location:
Surface Elevation:±305.0 feet NAVD88 ||
Termination Depth:7.0 ||
Proposed Location:Logged By:|299.0
Contractor:At Completion:|299.8
Rig Type:|--
Depth (ft.)Type
0.0
5.0
10.0
15.0
Infiltration Test in Adjacent
Augered Hole @ 6.5 fbgs
Test Pit TP-8 Terminated at Depth of 7.0 Feet Below Ground Surface.
LACUSTRINE Brown, Poorly Graded Sand with Silt (SP-SM)
SAND
3.5 1 Grab
SUBSOIL 27" Subsoil, Roots
TOPSOIL 9" Topsoil
(feet)(Classification)
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKS
Number
--
Test Method:Visual Observation Caterpillar 308E 24 Hours: --
Excavating Method:Compact Excavator JD 5.2 At Completion: --
(ft NAVD88)
SWM Area OR During:6.0
feet bgs Date Completed:11/9/2023 (feet bgs)(ft NAVD88)(feet bgs)
RECORD OF Test Pit No.:
SUBSURFACE EXPLORATION Page 1
Date Started:11/9/2023 Water Depth Elevation Cave-In Depth Elevation
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Test Pit Logs 11-9-23 12/22/2023
CPT Data Report
1 210 Maine Avenue Farmingdale, Maine 04344 | PO Box 515 Gardiner, Maine 04345 (Corporate)
64 Augusta Road Washington, Maine 04574 (Drilling Operations)
www.summitgeoeng.com
December 20, 2023
Summit #23337
Attn: Wendell "Wally" A. Shedd
Whitestone Associates, Inc.
352 Turnpike Road, Suite 105
Southborough, MA 01772
Reference: Geotechnical Exploration Services
Cone Penetration Testing – 3376 South Broadway, Saratoga Springs, NY
Dear Mr. Shedd;
Summit Geoengineering Services (SGS) has completed explorations for site development at
3376 South Broadway in Saratoga Springs, New York. This data report summarizes the results
of the seismic piezocone penetration testing (SCPTu).
Work Description
At the request of Whitestone Associates, SGS was asked to perform 2 seismic piezocone
penetration tests (SCPTu) to a depth of 100 feet or push refusal. The SCPTu explorations were
pre-marked and cleared of utilities by Whitestone Associates. SGS performed 2 SCPTu
explorations on December 19, 2023. CPTu was performed in accordance with ASTM D5778.
Shear wave velocity was performed in accordance with ASTM D7400. SCPTu was advanced using
a track mounted PowerProbe 9500 VTR with Vertek digital cone.
Performance of Seismic Cone Penetration Test (SCPTu)
CPT Data Report
2 210 Maine Avenue Farmingdale, Maine 04344 | PO Box 515 Gardiner, Maine 04345 (Corporate)
64 Augusta Road Washington, Maine 04574 (Drilling Operations)
www.summitgeoeng.com
SCPTu was conducted using a dual anchor with start of test at ground surface. Parameters
obtained include cone resistance (qc), sleeve friction (fs), piezocone pore pressure (u2), and
shear wave velocity (Vs). An exploration location plan and SCPTu output logs are attached to the
end of this data report. Excel output files are also provided in separate deliverable.
Push refusal within dense strata was encountered at a depth of 43 feet below ground surface
(BGS). Groundwater depth was measured within open SCPTu boreholes upon completion using
a water level meter. Water level ranged from 3.3 to 3.6 feet BGS. Equilibrium pore pressure was
measured by dissipation tests to estimate phreatic surface. Results are presented below:
PHREATIC DISSIPATION TEST SUMMARY MEASURED
Location Test Depth (ft) Phreatic Surface (ft) Groundwater Depth (ft)
CPT-1 17.8 2.5 3.6 CPT-1 43.6 3.6
CPT-2 14.5 2.6 3.3 CPT-2 43.1 4.7
Cross Sectional Area = 10 cm2, Pore Pressure Location = U2
Soil Behavior Type
Soil behavior type profiling is based on normalized cone penetration resistance (Robertson
1990). The subsurface conditions based on results of the cone penetration test predominately
of type 6 (clean sand to silty sand). Details of the profiling is shown on the attached SCPTu logs.
Shear Wave Velocity
Shear wave velocity tests were conducted at SCPTu rod break intervals using strike plates.
Performance of Shear Wave Velocity
CPT Data Report
3 210 Maine Avenue Farmingdale, Maine 04344 | PO Box 515 Gardiner, Maine 04345 (Corporate)
64 Augusta Road Washington, Maine 04574 (Drilling Operations)
www.summitgeoeng.com
Results of the shear wave velocity tests are provided on the graph below:
The average shear wave velocity (Vs) is 750 ft/s for the soil profile from 0 to 40 ft BGS. Increased
shear wave velocity of 2,900 ft/s was encountered at the end of push at dense strata or refusal.
Closure
SGS appreciates the opportunity to serve you during this phase of your project. If there are any
questions or additional information is required, please do not hesitate to call.
Sincerely yours,
Summit Geoengineering Services
Craig W. Coolidge, P.E.
Vice President
Principal Engineer
Attachments: EXPLORATION LOCATION PLAN, CPT LOGS, SHEAR WAVE RESULTS
0
10
20
30
40
50
0 500 1000 1500 2000 2500 3000Depth (ft)Velocity (ft/s)
Shear Wave Velocity (Vs)
CPT-1 CPT-2
GEOENGINEERING SERVICESSUMMIT
CPT Exploration Key
210 Maine Avenue Farmingdale, Maine 04344 | PO Box 515 Gardiner, Maine 04345 (Corporate)
64 Augusta Road Washington, Maine 04574 (Drilling Operations)
www.summitgeoeng.com
CPT EXPLORATION COVER SHEET
Piezocone penetration test (CPT) is performed by a cone on the end of a series of rods pushed into the ground at a
constant rate (2 cm/s) to obtain near continuous measurements of soil parameters. Parameters obtained during
the CPT test include cone tip resistance, sleeve friction, and piezocone pore pressure per ASTM D5778 and shear
wave velocity per ASTM D7400. These parameters are presented graphically on the CPT log.
CPT Data Symbols:
qc = Tip Resistance u2 = Pore Pressure qt = Total Resistance
fs = Sleeve Friction vs = Shear Wave Velocity ch = Coefficient of Consolidation
Soil Behavior Type:
Soil behavior type is interpreted from CPT data as one of 9 soil behavior types published by Robertson et al. 1990,
shown below. Each soil behavior type (SBT) is assigned a color which correlates to the SBT plot on the CPT log.
CPT-1COMPANY: Summit Geoengineering ServicesOPERATOR: S. FloydCREW: E.Stewart, P.ECLIENT: WhitestoneCLIENT REP: Oliver RogersTEST DATE: Tue 19/Dec/2023TEST ID: CPT-1PROJECT: 23337SITE: 3376 South BroadwayLOCATION: Saratoga Springs, NYTOTAL DEPTH: 43.853 ftPROBE ID: 4544.104XX Depth(ft)Tip COR(psi)FINAL BASELINE: -1.84 (psi)03500051015202530354045Sleeve Stress(psi)FINAL BASELINE: 0.2685 (psi)050Pore Pressure(psi) WT: 3.60(ft)FINAL BASELINE: -3.219 (psi)090Seismic Velocity(ft/s)03000Class. FR(Rob. 1990) 1 Sensitive, fine grained 2 Organic soils - peats 3 Clays - clay to silty clay 4 Silt mixtures - clayey silt to silty clay 5 Sand mixtures - silty sand to sandy silt 6 Sands - clean sand to silty sand 7 Gravelly sand to sand 8 Very stiff sand to clayey sand ** 9 Very stiff, fine grained ** *SBT: Robertson 1990; **Overconsolidated or Cemented; *SBT/SPT CORRELATION: UBC-198309Class. PP(Rob. 1990) 1 Sensitive, fine grained 2 Organic soils - peats 3 Clays - clay to silty clay 4 Silt mixtures - clayey silt to silty clay 5 Sand mixtures - silty sand to sandy silt 6 Sands - clean sand to silty sand 7 Gravelly sand to sand 8 Very stiff sand to clayey sand ** 9 Very stiff, fine grained ** *SBT: Robertson 1990; **Overconsolidated or Cemented; *SBT/SPT CORRELATION: UBC-198309REMARKSGroundwater @ 3.6 ftDissipation Test @ 17.8 ftPressure Head @ 2.5 ftDissipation Test @ 43.6 ftDissipation Head @ 3.6 ftAnchor Failure @ 43.9 ft
TEST ID: CPT-1
Depth 4.40ft
Ref*
Arrival 37.04mS
Velocity*
Depth 7.81ft
Ref 4.40ft
Arrival 40.56mS
Velocity 747.40ft/S
Depth 11.09ft
Ref 7.81ft
Arrival 49.40mS
Velocity 328.32ft/S
Depth 14.40ft
Ref 11.09ft
Arrival 51.64mS
Velocity 1378.68ft/S
Depth 17.81ft
Ref 14.40ft
Arrival 58.24mS
Velocity 494.21ft/S
Depth 21.03ft
Ref 17.81ft
Arrival 61.28mS
Velocity 1025.04ft/S
Depth 24.34ft
Ref 21.03ft
Arrival 66.08mS
Velocity 674.58ft/S
Depth 27.69ft
Ref 24.34ft
Arrival 71.16mS
Velocity 647.23ft/S
Depth 31.00ft
Ref 27.69ft
Arrival 75.88mS
Velocity 692.35ft/S
Depth 34.32ft
Ref 31.00ft
Arrival 79.96mS
Velocity 803.08ft/S
Depth 37.70ft
Ref 34.32ft
Arrival 84.32mS
Velocity 767.91ft/S
Depth 40.91ft
Ref 37.70ft
Arrival 88.40mS
Velocity 781.93ft/S
0 50 100 150 200 250 300
Depth 43.64ft
Ref 40.91ft
Arrival 89.32mS
Velocity 2940.02ft/S
Time (mS)
Hammer to Rod String Distance (ft): 4.92
* = Not Determined
PROBE ID: 4544.104XX
CPT-2COMPANY: Summit Geoengineering ServicesOPERATOR: S. FloydCREW: E.Stewart, P.ECLIENT: WhitestoneCLIENT REP: Oliver RogersTEST DATE: Tue 19/Dec/2023TEST ID: CPT-2PROJECT: 23337SITE: 3376 South BroadwayLOCATION: Saratoga Springs, NYTOTAL DEPTH: 43.183 ftPROBE ID: 4544.104XX Depth(ft)Tip COR(psi)FINAL BASELINE: -3.68 (psi)03500051015202530354045Sleeve Stress(psi)FINAL BASELINE: -0.3424 (psi)035Pore Pressure(psi) WT: 3.30(ft)FINAL BASELINE: -2.053 (psi)025Seismic Velocity(ft/s)03000Class. FR(Rob. 1990) 1 Sensitive, fine grained 2 Organic soils - peats 3 Clays - clay to silty clay 4 Silt mixtures - clayey silt to silty clay 5 Sand mixtures - silty sand to sandy silt 6 Sands - clean sand to silty sand 7 Gravelly sand to sand 8 Very stiff sand to clayey sand ** 9 Very stiff, fine grained ** *SBT: Robertson 1990; **Overconsolidated or Cemented; *SBT/SPT CORRELATION: UBC-198309Class. PP(Rob. 1990) 1 Sensitive, fine grained 2 Organic soils - peats 3 Clays - clay to silty clay 4 Silt mixtures - clayey silt to silty clay 5 Sand mixtures - silty sand to sandy silt 6 Sands - clean sand to silty sand 7 Gravelly sand to sand 8 Very stiff sand to clayey sand ** 9 Very stiff, fine grained ** *SBT: Robertson 1990; **Overconsolidated or Cemented; *SBT/SPT CORRELATION: UBC-198309REMARKSGroundwater @ 3.3 ftDissipation Test @ 14.5 ftPressure Head @ 2.6 ftDissipation Test @ 43.1 ftPressure Head @ 4.7 ftAnchor Failure @ 43.2 ft
TEST ID: CPT-2
Depth 4.40ft
Ref*
Arrival 28.76mS
Velocity*
Depth 7.78ft
Ref 4.40ft
Arrival 34.32mS
Velocity 468.19ft/S
Depth 10.99ft
Ref 7.78ft
Arrival 41.08mS
Velocity 420.15ft/S
Depth 14.44ft
Ref 10.99ft
Arrival 46.28mS
Velocity 617.15ft/S
Depth 17.78ft
Ref 14.44ft
Arrival 50.92mS
Velocity 689.46ft/S
Depth 21.16ft
Ref 17.78ft
Arrival 56.80mS
Velocity 557.07ft/S
Depth 24.57ft
Ref 21.16ft
Arrival 61.16mS
Velocity 764.98ft/S
Depth 27.85ft
Ref 24.57ft
Arrival 62.80mS
Velocity 1966.04ft/S
Depth 31.20ft
Ref 27.85ft
Arrival 69.56mS
Velocity 488.28ft/S
Depth 34.58ft
Ref 31.20ft
Arrival 74.52mS
Velocity 673.78ft/S
Depth 37.93ft
Ref 34.58ft
Arrival 78.36mS
Velocity 863.54ft/S
Depth 41.27ft
Ref 37.93ft
Arrival 82.84mS
Velocity 741.27ft/S
0 50 100 150 200 250 300
Depth 43.01ft
Ref 41.27ft
Arrival 83.44mS
Velocity 2878.51ft/S
Time (mS)
Hammer to Rod String Distance (ft): 4.92
* = Not Determined
PROBE ID: 4544.104XX
APPENDIX B
Laboratory Test Results
MM RWM
PL= LL= PI=
D90= D85= D60=
D50= D30= D15=
D10= Cu= Cc=
USCS= AASHTO=
*
0
10
20
30
40
50
60
70
80
90
100
GRAIN SIZE - mm.
0.0010.010.1110100
MM RWM
PL= LL= PI=
D90= D85= D60=
D50= D30= D15=
D10= Cu= Cc=
USCS= AASHTO=
*
0
10
20
30
40
50
60
70
80
90
100
GRAIN SIZE - mm.
0.0010.010.1110100
APPENDIX C
Supplemental Information
(USCS, Terms & Symbols)
Office Locations:
NEW JERSEY PENNSYLVANIA MASSACHUSETTS CONNECTICUT FLORIDA NEW HAMPSHIRE NEW YORK
500 CANAL VIEW BOULEVARD
SUITE 700
ROCHESTER, NY 14623
585.252.6879
whitestoneassoc.com
UNIFIED SOIL CLASSIFICATION SYSTEM
SOIL CLASSIFICATION CHART
MAJOR DIVISIONS
LETTER
SYMBOL
TYPICAL DESCRIPTIONS
COARSE
GRAINED
SOILS
MORE THAN
50% OF
MATERIAL IS
LARGER THAN
NO. 200 SIEVE
SIZE
GRAVEL AND
GRAVELLY SOILS
MORE THAN 50% OF
COARSE FRACTION
RETAINED ON NO. 4
SIEVE
CLEAN
GRAVELS
(LITTLE OR
NO FINES)
GW WELL-GRADED GRAVELS, GRAVEL-SAND
MIXTURES, LITTLE OR NO FINES
GP POORLY-GRADED GRAVELS, GRAVEL-
SAND MIXTURES, LITTLE OR NO FINES
GRAVELS WITH
FINES
(APPRECIABLE
AMOUNT OF
FINES)
GM SILTY GRAVELS, GRAVEL-SAND-SILT
MIXTURES
GC CLAYEY GRAVELS, GRAVEL-SAND-CLAY
MIXTURES
SAND AND SANDY
SOILS
MORE THAN 50% OF
COARSE FRACTION
PASSING NO. 4
SIEVE
CLEAN SAND
(LITTLE OR NO
FINES)
SW WELL-GRADED SANDS, GRAVELLY SANDS,
LITTLE OR NO FINES
SP POORLY-GRADED SANDS, GRAVELLY
SANDS, LITTLE OR NO FINES
SANDS WITH
FINES
(APPRECIABLE
AMOUNT OF
FINES)
SM SILTY SANDS, SAND-SILT MIXTURES
SC CLAYEY SANDS, SAND-CLAY MIXTURES
FINE
GRAINED
SOILS
MORE THAN
50% OF
MATERIAL IS
SMALLER THAN
NO. 200 SIEVE
SIZE
SILTS
AND
CLAYS
LIQUID LIMITS
LESS THAN 50
ML INORGANIC SILTS AND VERY FINE SANDS,
ROCK FLOUR, SILTY OR CLAYEY FINE
SANDS OR CLAYEY SILTS WITH SLIGHT
PLASTICITY
CL INORGANIC CLAYS OF LOW TO MEDIUM
PLASTICITY, GRAVELLY CLAYS, SANDY
CLAYS, SILTY CLAYS, LEAN CLAYS
OL ORGANIC SILTS AND ORGANIC SILTY
CLAYS OF LOW PLASTICITY
SILTS
AND
CLAYS
LIQUID LIMITS
GREATER
THAN 50
MH INORGANIC SILTS, MICACEOUS OR
DIATOMACEOUS FINE SAND OR SILTY
SOILS
CH INORGANIC CLAYS OF HIGH PLASTICITY,
FAT CLAYS
OH ORGANIC CLAYS OF MEDIUM TO HIGH
PLASTICITY, ORGANIC SILTS
HIGHLY ORGANIC SOILS PT PEAT, HUMUS, SWAMP SOILS WITH HIGH
ORGANIC CONTENTS
NOTE: DUAL SYMBOLS ARE USED TO INDICATE BORDERLINE SOIL CLASSIFICATIONS FOR SAMPLES WITH 5% TO 12% FINES
GRADATION* COMPACTNESS*
Sand and/or Gravel
CONSISTENCY*
Clay and/or Silt
% FINER BY WEIGHT RELATIVE
DENSITY
RANGE OF SHEARING STRENGTH IN
POUNDS PER SQUARE FOOT
TRACE........... 1% TO 10%
LITTLE.......... 10% TO 20%
SOME............ 20% TO 35%
AND............... 35% TO 50%
LOOSE. .................. 0% TO 40%
MEDIUM DENSE.... 40% TO 70%
DENSE................... 70% TO 90%
VERY DENSE........ 90% TO 100%
VERY SOFT....... LESS THAN 250
SOFT.................... ..... 250 TO 500
MEDIUM................... 500 TO 1000
STIFF..................... 1000 TO 2000
VERY STIFF.......... 2000 TO 4000
HARD...... GREATER THAN 4000
* VALUES ARE FROM LABORATORY OR FIELD TEST DATA, WHERE APPLICABLE.
WHEN NO TESTING WAS PERFORMED, VALUES ARE ESTIMATED.
L:\Geotechnical Forms and References\Reports\USCSTRMSSYM - Rochester.docx
Office Locations:
NEW JERSEY PENNSYLVANIA MASSACHUSETTS CONNECTICUT FLORIDA NEW HAMPSHIRE NEW YORK
500 CANAL VIEW BOULEVARD
SUITE 700
ROCHESTER, NY 14623
585.252.6879
whitestoneassoc.com
GEOTECHNICAL TERMS AND SYMBOLS
SAMPLE IDENTIFICATION
The Unified Soil Classification System is used to identify the soil unless otherwise noted.
SOIL PROPERTY SYMBOLS
N: Standard Penetration Value: Blows per ft. of a 140 lb. hammer falling 30" on a 2" O.D. split -spoon.
Qu: Unconfined compressive strength, TSF.
Qp: Penetrometer value, unconfined compressive strength, TSF.
Mc: Moisture content, %.
LL: Liquid limit, %.
PI: Plasticity index, %.
δd: Natural dry density, PCF.
▾: Apparent groundwater level at time noted after completion of boring.
DRILLING AND SAMPLING SYMBOLS
NE: Not Encountered (Groundwater was not encountered).
SS: Split-Spoon - 1 ⅜” I.D., 2" O.D., except where noted.
ST: Shelby Tube - 3” O.D., except where noted.
AU: Auger Sample.
OB: Diamond Bit.
CB: Carbide Bit
WS: Washed Sample.
RELATIVE DENSITY AND CONSISTENCY CLASSIFICATION
Term (Non-Cohesive Soils) Standard Penetration Resistance
Very Loose 0-4
Loose 4-10
Medium Dense 10-30
Dense 30-50
Very Dense Over 50
Term (Cohesive Soils) Qu (TSF)
Very Soft 0 - 0.25
Soft 0.25 - 0.50
Firm (Medium) 0.50 - 1.00
Stiff 1.00 - 2.00
Very Stiff 2.00 - 4.00
Hard 4.00+
PARTICLE SIZE
Boulders 8 in.+ Coarse Sand 5mm-0.6mm Silt 0.074mm-0.005mm
Cobbles 8 in.-3 in. Medium Sand 0.6mm-0.2mm Clay -0.005mm
Gravel 3 in.-5mm Fine Sand 0.2mm-0.074mm
L:\Geotechnical Forms and References\Reports\USCSTRMSSYM - ROCHESTER .docx
Office Locations:
NEW JERSEY PENNSYLVANIA NEW YORK CONNECTICUT FLORIDA NEW HAMPSHIRE NEW YORK
500 CANAL VIEW BOULEVARD
SUITE 700
ROCHESTER, NY 14623
585.252.6879
whitestoneassoc.com
P R O P O S A L
December 11, 2023
via email
WL ENTERPRISES ACQUISITIONS, LLC
c/o SNYDER, KILEY, TOOHEY, CORBETT & COX, LLP
160 West Avenue
Saratoga Springs, New York 12866
Attention: Ms. Sarah Morin
Chief Growth Officer
Regarding: SUPPLEMENTAL GEOTECHNICAL INVESTIGATION
3376 SOUTH BROADWAY
TAX MAP NO.: 178-2-15
SARATOGA SPRINGS, SARATOGA COUNTY, NEW YORK
WHITESTONE PROPOSAL NO.: PRY30830G.M23
Dear Ms. Morin:
Whitestone Associates Engineering & Geology NY, PLLC (Whitestone) is pleased to submit this r proposal
to conduct a supplemental geotechnical investigation at the above-referenced site. This proposal replaces
Whitestone’s original proposal dated September 21, 2023 and is based on the September 13, 2021 Boundary
Survey prepared by NMB Land Survey, PLLC, recent correspondence, experience with similar projects,
and available aerial imagery.
PROJECT DESCRIPTION
The approximately 10.67-acre subject property located at 3376 South Broadway in Saratoga Springs,
Saratoga County, New York is agricultural land. The property is identified further by the City of Saratoga
Springs Assessor’s Office as Tax Map No. 178-2-15 and is being evaluated for development with a 40,000-
square feet footprint brewery/restaurant with patio and associated asphalt paved parking and access drives.
The proposed location and orientation of the structure has not been confirmed. A supplemental
geotechnical investigation has been requested to provide general foundation and earthwork
recommendations.
For the purposes of this proposal, cuts and fills on the order of up to two feet are anticipated, and maximum
design loads are assumed to be less than the following: column load - 150 kips, wall load - 4.0 kips/linear
foot, and floor load - 200 pounds per square foot. Pavement loads are estimated to be 25,000 (18) kip
equivalent single axle loads.
WL Enterprises Acquisitions, LLC
c/o Snyder, Kiley, Toohey, Corbett & Cox, LLP
Supplemental Geotechnical Investigation Proposal
3376 South Broadway
Saratoga Springs, New York
December 11, 2023
Page 2
Environmental & Geotechnical Engineers & Consultants
SCOPE OF SERVICES
In order to provide supplemental soils information relevant to potential cost-impactive or development-
impactive subsurface considerations, Whitestone will conduct a supplemental geotechnical investigation
by means of seismic cone penetration testing (CPT). The scope of this supplemental investigation will be
conducted to evaluate seismic Site Class and the liquefaction potential of the underlying soils. Whitestone’s
proposed supplemental subsurface exploration will include the following:
► advancing up to two CPT soundings with shear wave velocity testing within the proposed building
area to a depth of up to 60 feet below ground surface, or refusal;
► identifying pertinent physical and engineering characteristics of the subsurface materials
encountered during sampling and testing; and
► providing an opinion regarding geotechnical considerations for developing the site.
Whitestone’s proposed investigation and laboratory program will be supervised by a Whitestone
engineer/geologist who will observe site and surrounding conditions, direct testing programs, review
subsurface conditions, and classify the subsurface materials encountered. The results of the geotechnical
investigation will be presented in a Supplemental Report of Geotechnical Investigation prepared by a
Professional Engineer.
PLANNING ASSUMPTIONS
Whitestone assumes free access will be granted to the subject property for the duration of the one-day
project. The boring locations must be accessible to a track-mounted CPT rig during the hours of 7:00 AM
to 5:00 PM, Monday through Friday. Whitestone’s cost proposal assumes using non-union labor.
Whitestone will coordinate a mark-out of on-site public utilities and, if authorized, engage a private utility
locator, however, the site owner must establish all private utilities. Whitestone assumes no responsibility
for the location of or damage to private underground utilities not clearly marked by the site owner prior to
commencement of site services.
Borings will be backfilled once with excavated soil, and borings will be restored surficially with asphalt
cold patch or Portland cement concrete, where appropriate. Costs for repaving test locations or repairing
areas disturbed by the field investigation are not included in this proposal. The owner should anticipate
some settlement at test locations, and future maintenance may be required. Excess soil will remain on site
(either mounded at test locations or placed at a staging area designated by the site owner) or can be drummed
at an additional cost, if requested by the client. Whitestone assumes no responsibility for damage resulting
from future settlement at backfilled locations. Unless otherwise requested by the client, all geotechnical
soil samples will be disposed 60 days following completion of field investigation efforts.
This proposal is based on the assumption that conditions suitable for foundation design recommendations
will be encountered within the exploration depths proposed. If marginal or unsuitable conditions are
encountered, the exploration program may be revised to include deeper borings and/or additional
investigation and analysis may be recommended at an additional cost. If possible, Whitestone will attempt
to make necessary revisions to the exploration program during the site investigation.
WL Enterprises Acquisitions, LLC
c/o Snyder, Kiley, Toohey, Corbett & Cox, LLP
Supplemental Geotechnical Investigation Proposal
3376 South Broadway
Saratoga Springs, New York
December 11, 2023
Page 3
Environmental & Geotechnical Engineers & Consultants
COST PROPOSAL
Whitestone will conduct the supplemental geotechnical engineering services as outlined above for the lump
sum of $16,500.00, excluding reimbursable expenses:
Additional consultation or engineering services including attending meetings, participating in conference
calls, preparing supplemental correspondence and/or budgetary cost projections or other activities not
specified will be billed in addition to the pricing above.
This proposal is subject to the Terms and Conditions outlined above and as attached hereto, and costs are
exclusive of reimbursable expenses not specified above. Any additional services or out-of-scope work
items will be confirmed in writing and invoiced in accordance with Whitestone’s Professional Services
Rate Schedule (copy attached) or a supplemental quotation. Please acknowledge your acceptance of this
proposal by signing where indicated below.
Whitestone appreciates the opportunity to present a proposal for this project and looks forward to being of
continued service to WL Enterprises Acquisitions, LLC and Snyder, Kiley, Toohey, Corbett & Cox, LLP.
Please contact us with any questions regarding this proposal.
Sincerely,
WHITESTONE
Jason R. Landry Ryan R. Roy, P.E.
Senior Project Manager Vice President
WAS/th N:\Proposal Folders\2023\PRY30830G.M23\Proposals and Contracts\SaratogaSpringsNY-Supplemental GI(PRY30830G.M23).docx
Enclosures
ACCEPTED:
WL ENTERPRISES ACQUISITIONS, LLC
c/o SNYDER, KILEY, TOOHEY, CORBETT &
COX, LLP
By: _____________________________________
(Signature)
_____________________________________
(Print Name)
Title: _____________________________________
Date: _____________________________________
Page 1 of 3
December 11, 2023 (the “Effective Date”)
STANDARD TERMS AND CONDITIONS (the “Terms and Conditions”)
These Terms and Conditions form a part of the proposal of WHITESTONE ASSOCIATES ENGINEERING & GEOLOGY NY, PLLC and/or
WHITESTONE ASSOCIATES, INC. (collectively, the "Firm"), and WL ENTERPRISES ACQUISITIONS, LLC c/o SNYDER, KILEY, TOOHEY,
CORBETT & COX, LLP (the "Client"):
I. INTERPRETATION AND CONSTRUCTION.
A. The Firm is involved in the business of providing professional engineering and professional geologist services, which may include
environmental, geotechnical and construction support services. Client seeks to engage the Firm, and the Firm accepts such engagement, to provide
various types of services on Client’s projects (each a “Project”) pursuant to the terms hereof and each separate proposal (each a “Proposal”) to be
executed by the parties.
B. The parties desire for these Terms and Conditions to govern the relationship between the parties. Unless otherwise specifically set forth in a
Proposal, in the event of a conflict or inconsistency betwee n the Terms and Conditions and a Proposal, the Terms and Conditions shall take
precedence, govern and control. The parties hereby acknowledge that these Terms and Conditions shall be incorporated by reference into each
Proposal, as if fully set forth at length therein. The Terms and Conditions, collectively with the Proposal shall be referred to herein as the “Agreement”.
II. THE SERVICES.
A. Client hereby retains the Firm to provide the services as set forth in one or more Proposals (hereinafter the “Services”). The “Services” shall
also include any additional or different services requested by the Client and the provision of which is agreed-upon by the Firm.
B. In the event that the Proposal includes the provision of Services to be provided by one or more Li censed Site Remediation Professionals
(“LSRP”), the LSRP Rider shall be incorporated herein and made a part hereof.
C. In the event that the Proposal includes the provision of underground storage tank services, the Underground Storage Tank Serv ices Rider
shall be incorporated herein and made a part hereof.
III. PROFESSIONAL RESPONSIBILITY. The Firm represents that the Services shall be performed within the limits described in accordance with the
“Scope of Services” contained in the Proposal, and in a manner consistent with that level of care and skill ordinarily exerc ised by comparable
professional firms under similar circumstances at the time the Services are performed. No other representations to the Client, expressed or implied, and
no warranty or guarantee is included or intended hereunder, or in any report, opinion, document or otherwise. The Firm does not guarantee the ultimate
approval or success of the Client's Project. The Firm is not liable for consequential punitive, compensatory, incidental, liquidat ed or delay damages
caused by the ultimate approval or succ ess of the Client's Project or time lines of the completion of the Services. The Firm's Services cannot be
construed to be, and are not, a guarantee or assurance Client will have no or any reduced level of environmental liabilities or that undetected
environmental problems do not exist or will not arise in the future.
IV. CLIENT RESPONSIBILIT Y. Client will provide to the Firm all available information material, data, and assistance for performance of the Services
in compliance with all applicable laws, inc luding and w ithout limitation, previous repor ts and any other data affecting the site upon which the Services
are to be performed (the “Site"). In the event that Client does not own the Site, Client represents and warrants that Client, Client’s agents, employees,
staff, consultants, contractors and subcontractors, have been granted a right of entry to the Site as is necessary for the Firm’s performance of the
Services. Client will ensure that access to the Site is available to the Firm at all reasonable times, and Client will make available to the Firm’s
representatives those of Client’s employees, if any, who are knowledgeable concerning the Site. Client will designate in writing the person to act as
Client’s representative with respect to the Services to be perfor med, and such person will have complete authority to transmit instructions, receive
information, and interpret and define Client’s policies and decisions with respect to the Services. The Firm shall be entitled to rely upon all information
obtained from Client. The Firm does not assume contr ol of or responsibility for the Site or the person in charge of th e Site, or undertake any
responsibility other than that required by law, for reporting to any federal, state, or local agencies any conditions at the Site that may present an actual
or potential danger to public health, safety, or the environment.
V. PAYMENT TERMS. Invoices for Professional Services and expenses incurred s hall be generated on a monthly basis, and are due and payable
within 30 days of receipt. If an invoice becomes delinquent, the Firm reserves the right to cease all services and pursue all remedies upon three (3)
days prior written notice to Client. Client shall release, indemnify and hold the Firm harmless from and against any and all damages of any kind
whatsoever resulting from a cessation of the Services for Client’s failure to make payment in accordance with this Agreement. In the event the Firm
seeks legal action against Client in connection with Client’s payment obligations under this Agreement, the Client shall reimburse the Firm for all costs
of collection, including but not limited to, all costs an expenses (including reasonable attorneys ’ fees) and any other related expenses in connection with
such action. Further, the Client agrees to pay the Firm the full portion of any and all unpaid amounts plus an interest charge equal to 1.5% per month of
all monies thirty (30) days past due, up to and including the time of payment. In the event a retainer is requested by the Firm, th ose monies will be
applied to the final invoice generated by the Firm. Any excess amount will be refunded to the Client within 14 days after the Firm’s receipt of payment.
VI. NOTIFICATION OF HAZARD S. Client shall inform the Firm of any known potentially hazardous substance, environmental contamination, or
condition that presents or could present a potential danger to human health or the environmen t, which exists in, at, or near the Site (collective ly,
“Hazards”). Client releases and shall indemnify, defend and hold harmless the Firm and each Firm Covered Person from and against any and all
Losses (as defined in Section XII hereof), including Losses for personal injury, disease, initial and ongoing medical expenses, including, but not limited
to, continued health monitoring, death, property damage and economic-based claims that arise out of (a) Client’s failure to advise the Firm of Known
Hazards, or (b) unanticipated occurrence of H azards discovered during the provision of the Services.
VII. JOB SITE HEALTH AND SAFETY. The Firm’s sole responsibility for maintaining compliance with the Occupational Safety and Health Act of
1970, as amended, and the rules, standards and regulations promulgated thereunder (collectively, “OSHA”) is to ensure compliance with such OSHA
rules and regulations by Firm employees and Subcontractors. The Firm shall not be responsible for OSHA compliance as it a pplies to any other party
not under Firm’s control. Without limiting the generality of the foregoing, the Firm shall have no responsibility for OSHA compliance by or relating to
Client or any party providing services on the Site, or any employee, agent, representative, officer, director, owner , or independent contractor of any of
the foregoing parties.
Page 2 of 3
VIII. BURIED UTILITIES; SITE DISTURBANCE. Client shall notify the Firm of the location of all known private subsurface utility lines, man-made
objects and underground structures located beneath the Site. Prior to conducting any subsurface work, the Firm will call the local utility “One Call”
services and engage an underground marking and utility locator service (if authorized by Client) in an attempt to locate subsurface utility lines and other
man-ma de objects that may exist beneath the Site. Client recognizes that the Firm’s research may not identify all subsurface utility lines, man-made
objects and underground structures. The Firm will take commercially reasonable precautions to avoid damage or injury to any subsurface u tilities or
structures known to the Firm. Client further recognizes that subsurface conditions may vary from those encountered at the location of the Site where,
and at the time when, borings, sampling, or testing are performed by the Firm in connection with its Site research, and that the data provided by the
Firm are based solely on the information available to the Firm. Client acknowledges that the equipment used to perform the Services may affect, alter,
or damage the terrain, vegetation, buildings, structures, and equipment in, at, or on the Site.
Firm shall backfill each test location once with soil excavated from the Site and shall patch the upper surface of paved areas above the location from
which the test boring was obtained with cold-patch asphalt and/or grout. Such patches and the location and surrounding proximate surface,
subsurface, horizontal and vertical area will require ongoing and continuous supervision, inspection , maintenance and repair. Firm assumes no
responsibility for damage res ulting from future settlement at any or all of the test areas and/or patches and the surrounding proximate surface,
subsurface, horizontal and vertical area thereof.
IX. PUBLICATIONS. Client agrees that the Firm may use and publish a general description of the Services performed by the Firm in advertising and
qualifications, which advertising may include, witho ut limitation, brochures and other promotional material (including print and electronic media). Client’s
covenants contained in this Section IX will survive the termination of this Agreement.
X. OWNERSHIP OF DOCUMENTS. All reports, field data, notes, calculations, estimates, drawing documents and other items pr epared by the Firm
are instr uments of service and shall remain the joint property of the Firm and the Client. Client agrees that all reports and other work furnished to the
Client or its agents, which are not paid for will be returned upon demand, and will not be used for any other purposes whatsoever. The Firm will retain
all pertinent r ecords r elated to the Services performed during which period, the records will be made available to the Client at r easonable times,
providing no outstanding account balances exist. Items prepared by the Firm are not intended for use other than for the above Project. Use in any other
Project or reuse by the Client for other Projects will be at Client's sole risk. Any el ectronic media and documents on computer disk prepar ed by the Firm
are subject to use only by express writ ten permission by the Firm, and are not considered the Client's property. In the event the Client utilizes this
information without written permission, or utilizes any of the Firm's work product in any fashion specifically not authorized by the Firm, the Client does
so at their own risk and shall defend, indemnify and hold the Firm harmless for any damages or claims that may arise as a result of such utilization.
XI. DISCLOSURE TO THIRD PARTIE S. Client acknowledges that the Services may be subject to State, Regional or Federal reporting requirements
and the reporting and notification requirements thereof. The Firm’s technical and pricing information are confidential and proprietary information of the
Firm and Client may not disclose such information without the Firm's express prior written consent.
XII. INDEMNIFICATION. Client and Firm release and agree to indemnify and hold harmless each other and each of their officers, directors, agents,
employees, consultants and each of their respective successors and assigns (collectively, the “Covered Persons”) from and against any and all claims,
liabilities, losses, proceedings, suits, actions, damages or ex penses of any kind (under any theory under contract, tort, statue alleging negligence,
errors, omissions, strict liability, statutory liability, breach o f c ontract, breach of warranty, negligent misrepresentations, or any other theory), including
consequential, incidental, special, exemplary and punitive damages, and also including court costs and reasonable attorneys’ fees (collectively
“Losses”) which arise out of any (i) negligent or willful acts or omissions by the Client’s or Firm’s owners, agents, directors, officers and employees, (ii)
breach of this Agreement by the Client’s or Firm’s owners, agents, directors, officers and employees, (iii) personal injury or property injury claims
relating to the Services, the Site or any Hazards, (iv) violations by the Client’s or Firm’s owners, agents, directors, officers and employees, of any
federal, state or local law, regulation or rule, whether or not such violations arise out of, or occur in connection with, the Services.
XIII. TERM AND TERMINATION.
A. Term. This Agreement shall be in effect as of the Effective Date and shall remain in effect until the anniversary thereof (the “Term”) or until
such later date as may be set forth in a Proposal (it being understood that th is Agreement will not terminate in the event the term set forth in a Proposal
is longer than the term set forth herein). Thereafter, this Agreement will automatically renew for additional periods of one year each (each an
“Additional Term”), unless either party notifies the other party in writing at least sixty (60) days prior to the end of the Term or applicable Additional Term
of its intent not to renew.
B. Termination.
1. This Agreement may be terminated by either party upon fourteen (14) days' written notice, should any terms not be performed in accordance
with this Proposal. In the event of termination, the Firm shall be paid in full for (i) the Services rendered through the actual date of termination (ii) for
any unpaid expenses, and (iii) reasonable expens es incurred by the Firm from such termination, including, but not limited to, reasonable winding down
expenses.
2. Termination by Client shall be by written notice to Thomas K. Uzzo, Whitestone Associates, Inc., 30 Independence Boulevard, Suite 250,
Warren, New Jersey 07059, tuzzo@whitestoneassoc.com. Termination by the Firm shall be made by written notice to the addressee of this Agreement.
Such notice of termination will become effective when rec eived by the non-terminating party unless a later date is specified therein.
XIV. LIMITATION OF LIABILITY; DISCLAIMER OF WARRANTIES.
A. The Firm shall only be responsible for delivering the Services to Client. The Firm, acting in good faith, shall not be liabl e for any action,
omission, or loss in connection with the Agreement.
B. DISCLAIMER OF WARRANTIES. EXCEPT AS SET FORTH IN SECTION III (“PROFESSIONAL RESPONSIBILITY”) OF THESE TERMS
AND CONDITIONS, THE FIRM MAKES NO OTHER WARRANTIES, GUARANTEES OR REPRESENTATIONS WITH RESPECT TO THE SERVICES
OR OTHERWISE AND THE FIRM HEREBY DISCLAIMS ANY AND ALL WARRANTIES AND REPRESENTATIONS, WHETHER EXPRESS OR
IMPLIED, INCLUDING, WITHOUT LIMITATION, ALL WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
C. LIMITATION OF LIABILITY. THE FIRM’S ENTIRE LIABILITY TO CLIENT FOR DAMAGES CONCERNING PERFORMANCE OR
NONPERFORMANCE BY THE FIRM, OR IN ANY WAY RELATED TO A PROJECT, AND REGARDLESS OF WHETHER THE CLAIM FOR SUCH
DAMAGES IS BASED IN CONTRACT, TORT, STRICT LIABILIT Y OR OTHERWISE (INCLUDING WITHOUT LIMITATION, NEGLIGENCE), SHALL
NOT EXCEED THE TOTAL FEES ACTUALLY PAID TO THE FIRM BY CLIENT UNDER THE TERMS OF THE PROPOSAL THAT COVERS THE
Page 3 of 3
PROJECT THAT SERVES AS THE BASIS FOR THE CLAIM. IN NO EVENT SHALL ANY FIRM COVERE D PERSON BE LIABLE FOR ANY
INDIRECT, INCIDENTAL, SPECIAL, CONSEQUENTIAL, EXEMPLARY, OR PUNITIVE DAMAGES, COS TS, EXPENSES, OR LOSSES OF ANY KIND
WHATSOEVER. IN ADDITION, IN NO EVENT SHALL ANY FIRM COVERED PERSON BE LIABLE FOR ANY ACTIONS, DAMAGES, CLAIMS,
LIABILITIES, COSTS, EXPENSES, OR LOSSES OF ANY KIND WHATSOEVER IN ANY WAY ARISING OUT OF OR RELATING TO ANY OR ALL
ACTS OR OMISSIONS OF CLIENT AND/OR ANY THIRD PARTY, ANY DAMAGE CAUSED BY CLIENT AND/OR ANY THIRD PARTY, OR ANY
INJURY TO CLIENT, AND/OR ANY TH IRD PARTY, IN CONNECTION WITH OR RELATED TO THE SERVICES, OR THE FIRM’S PERFORMANCE
HEREUNDER. THE PROVISIONS OF THIS SECTION SHALL APPLY REGARDLESS OF THE FORM OF ACTION, DAMAGE, CLAIM, LIABILITY,
COST, EXPENSE, OR LOSS, WHETHER IN CONTRACT, TORT, STRICT LIABILITY OR OTHERWISE (INCLUDING, WITHOUT LIMITATION,
NEGLIGENCE).
XV. TESTIMONY. Client shall compensate the Firm at the Firm’s applicable hourly rate in the event that the Firm or any of its personnel agrees or is
compelled to testify and/or provide docu ments in any lawsuit or legal action related to this Agreement, the Services or the Site. In addition, Client shall
reimburse the Firm for all reasonable actual out-of-pocket expenses incurred by the Firm in connection with responses to subpoenas and othe r similar
legal orders issued to the Firm in respect to the Services performed under this Agreement. This provision shall survive the termination or expiration of
this Agreement.
XVI. NON-SOLICITATION OF FIRM PERSONNEL. Firm and Client will not solicit the employees or independent contractors of the other to become
employees or consultants during the Term and for a one (1) year period following the termination or expiration thereof.
XVII. REVOCATION OF CERTIFICATION OR STATEMENTS. The Firm shall have the right to revoke any certification, statements, or professionally
sealed documents or plans in the event the Firm is made aware of unauthorized, prohibited use by the Client. The Client assumes the risk of any
damages and any and all claims that may occur as a result of the unauthorized use of the Firm's documents.
XVIII. LIMITATION PERIOD. No lawsuit shall be brought by Client against the Firm for damages for any negligent professional acts, errors, or
omissions, or breach of contract unless commenced within twenty-four (24) months from the last date of services provided under this Agreement.
XIX. INTEGRATION. This Agreement constitutes the entire understanding and agreement between Client and the Firm and shall not be altered or
modified except by an agreement, in writing, signed by both Client and the Firm. This Agreement s hall supersede all prior negotiations, understandings,
and agreements, whether oral or written, and such prior agreements shall thereupon be null and void and without legal effect.
XX. ASSIGNMENT. This Agreement shall be binding upon the parties, their suc cessors, representatives, and assigns. Client sha ll not assign or
transfer this Agreement or any interest herein without the prior written consent of the Firm. The Firm may not assign or transfer this Agreement to any
party without the prior written consent of Client, which consent shall not be unreasonably withheld. Further Firm may, without the consent of Client,
subcontract any portion of the Services hereunder.
XXI. SEVERABILITY. The provisions of this Agreement shall be severable, and if any provision hereof shall be determined by any court or competent
jurisdiction to be invalid, such determination shall not affect or invalidate the remainder hereof.
XXII. ENTIRE AGREEMENT. Each party hereto acknowledges its full understanding of this Agreement, that there are no verbal promises,
understandings or agreements in connection herewith. This Agreement may be modified by the written consent of the parties heret o.
XXIII. GOVERNING LAW; VENUE; ALTERNATIVE DISPUTE RESOLUTION. This Agreement shall be governed by and construed in accordance
with the laws of the State of New York. Any dispute, controversy or claim arising out of or in connection with this Agreement or any breach or alleged
breach hereof shall, upon the request of any party involved, be submitted to, and settled by, binding arbitrat ion and shall be privately administered by a
single arbitrator who shall administer the arbitration pursuant to the commercial arbitration rules then in effect of the American Arbitration Association
that are applicable to a privately administered arbitration.
XXIV. WASTE MATERIAL. Where waste materials are to be handled, transported, treated, and/or disposed o f by the Firm, Client agrees to
accurately and completely describe said waste in writing to the Firm and warrants to the Firm that the waste material conforms to the specification and
description set forth on the descriptions thereof. Legal responsibility and liability for waste material not reasonably conformin g to the specifications and
descriptions set forth in the written description shall at all times remain with the waste generator. The Client shall review documentation for accuracy
upon receipt and notify the Firm immediately of any inaccuracies.
XXV. SAMPLE RETENTION/DISPOSAL. All samples of uncontaminated soil, rock, and water may be discarded thi rty (30) days after submission of
the Firm's final report unless Client advises the Firm to deliver to th e samples to Client at Client's sole expense, or to store them for an agreed upon
charge. In the event that samples and/or materials contain or are suspected to contain substances or c onstituents hazardous or detrimental to health,
safety, or the environment, as defined by federal, state, or local statutes, regulations, or ordinances the Firm will, after completion of testing and at
Client's expense, ret urn such samples and materials to Client, or (using a manifest signed by Client as generator and transpor ter) transport such
samples and materials to a location s elected by Client for final disposal. Client agrees to pay all cos ts associated with the storage, transport, and
disposal of samples and materials. Client recognizes and agrees that the Firm is actin g as a bailee and at no time assumes title to said waste.
XXVI. DURATION OF FEE SCHEDULE. The fee schedule included in a Proposal shall remain in full force and effect for a period of ninety (90) days
from the date of the proposal. If the Proposal is accepted and executed within such ninety (90) day period, then the fee schedule included in that
Proposal shall remain in full force and effect for a period of one year from the date of that Proposal. If the Proposal is not accepted and executed within
such ninety (90) day period, the Firm shall have the right to revise the fee scheduled in its discretion, which may include, but not be limited to, revising
the fee schedule included in that Proposal, increase its fees for Services, and adjusting the time for and scheduling of performance of services.
XXVII. COMPLIANCE WITH LAW. In the performance of each party’s obligations under this Agreement, each of the Firm and Client agree to comply
with all applicable federal, state, and local laws, rules, regulations, and orders of any duly constituted authority.
Office Locations:
NEW JERSEY PENNSYLVANIA MASSACHUSETTS CONNECTICUT FLORIDA NEW HAMPSHIRE NEW YORK
PROFESSIONAL SERVICES RATE SCHEDULE - 2023
Executive (President or Vice President) $ 295.00/hour
Senior Associate $ 275.00/hour
Associate $ 250.00/hour
Expert Witness Testimony $ 350.00/hour
Senior Professional Engineering Manager $ 225.00/hour
LSRP/LSP/LEP $ 215.00/hour
Project Manager $ 195.00/hour
Professional Engineer $ 195.00/hour
PCA Manager $ 195.00/hour
Senior Professional Geologist $ 195.00/hour
Associate Project Manager $ 175.00/hour
Professional Geologist $ 175.00/hour
Environmental Engineer $ 165.00/hour
Geotechnical Engineer $ 165.00/hour
Environmental Specialist/Scientist $ 150.00/hour
Geologist $ 130.00/hour
Project Engineer $ 130.00/hour
Asbestos or Lead Paint Inspector $ 130.00/hour
Wetlands Scientist $ 125.00/hour
ICC/DCA Inspector $ 115.00/hour
Environmental Technician $ 95.00/hour
Staff Engineer/Inspector $ 95.00/hour
Technical Assistant $ 90.00/hour
CADD Operator/Draftsman $ 90.00/hour
Project Coordinator $ 85.00/hour
Administrative Assistant $ 65.00/hour
Clerical Assistant $ 55.00/hour
Travel/Mileage $ 0.655/mile + tolls
Notes:
1. Mileage reimbursement subject to change based upon IRS standard mileage reimbursement rate.
2. Additional project-specific equipment, materials, and/or laboratory analyses or subcontracted services will be
quoted on a case-by-case basis.
3. All rates are billed portal-to-portal.
4. Projects located greater than 100 miles from a Whitestone office may be subject to per diem expenses.
5. Construction phase testing and inspection services are subject to a four-hour minimum charge per day.
1 1
Project:
Location:
Surface Elevation:±||
Termination Depth: Date Completed:| |
Proposed Location:| --
At Completion:| -- --|
| --24 Hours: --|
No Type
0.0
5.0
10.0
15.0
16.0
20.0
25.0
WOH
/12"SUBSOIL
2 2 28
7
4
3 4 3
2 1 3 2
3 3 2 2
1 1 17 2
2 - 4
4 - 6
6 - 8
8 - 10 S-5
S-4
S-3
S-2
3 - -
5
3
15
20
18
2 -
-
As Above, Loose (SP-SM)
As Above, Very Loose to Loose (SP-SM)
As Above, Loose (SP-SM)
As Above (SP-SM)-10 - 12 S-6 3 16 6
20 2415 - 17 S-7
10 - 4
6 - 8 -
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
RECORD OF Boring No.: B-1
SUBSURFACE EXPLORATION Page of
Elevation
20.7 feet bgs 11/8/2023
(feet bgs) (ft NAVD88) (feet bgs) (ft NAVD88)
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NS feet Above NAVD88 Date Started:11/8/2023 Water Depth Elevation Cave-In Depth
--Drill / Test Method:HSA / SPT (Autohammer)Contractor:CC --
Building Logged By:OR During:6.0
At Completion:
-- --
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKSDepth
(feet)Blows Per 6"
Rec.
(in.)N (feet)(Classification)
Equipment:Geoprobe 7822DT 24 Hours:
TS 6" Topsoil
18" Subsoil, Roots
Brown, Very Loose, Poorly Graded Sand with Silt (SP-SM)
TILL
As Above, Very Dense
Boring B-1 Terminated at a Depth of 20.7 Feet Below Ground Surface.
0 - 2 S-1
3 1
- -
- - -
- - -
- - -
16 -
40/
5"
As Above, Medium Dense (SP-SM)
Brown, Dense, Silty Sand with Gravel (SM)
GLACIAL
LACUSTRINE
DEPOSIT
20 - 20.7 S-8 51 - 40/2" 7 -
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Boring Logs 10-8-23.xlsx 11/22/2023
1 1
Project:
Location:
Surface Elevation:±||
Termination Depth: Date Completed:| |
Proposed Location:| --
At Completion:| -- --|
| --24 Hours: --|
No Type
0.0
5.0
10.0
15.0
20.0
25.0
LACUSTRINE
As Above (SP-SM)17 5
1/12"
1 1
DEPOSIT
As Above, Medium Dense (SP-SM)
Boring B-2 Terminated at a Depth of 22 Feet Below Ground Surface.
15 - 17 S-5 1 1 16 2 As Above (SP-SM)
1 22 18 - 10 S-4 1
45 - 7 S-3 3
As Above, Very Loose (SP-SM)
Brown, Loose, Poorly Graded Sand with Silt (SP-SM)
3 2
SUBSOIL 18" Subsoil, Roots
2 - 4 S-2 3 3 4 5 13 7
0 - 2 S-1 11 10 19 192 8
TS 12" Topsoil
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKSDepth
(feet)Blows Per 6"
Rec.
(in.)N (feet)(Classification)
--Equipment:Geoprobe 7822DT 24 Hours: --
Drill / Test Method:HSA / SPT (Autohammer)Contractor:CC --At Completion: --
Building Logged By:OR During:6.0
Elevation
22.0 feet bgs 11/8/2023
(feet bgs) (ft NAVD88) (feet bgs) (ft NAVD88)
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NS feet Above NAVD88 Date Started:11/8/2023 Water Depth Elevation Cave-In Depth
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
RECORD OF Boring No.: B-2
SUBSURFACE EXPLORATION Page of
20 - 22 S-6 2 3 8 9 12 11
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Boring Logs 10-8-23.xlsx 11/22/2023
1 1
Project:
Location:
Surface Elevation:±||
Termination Depth: Date Completed:| |
Proposed Location:| --
At Completion:| -- --|
| --24 Hours: --|
No Type
0.0
5.0
10.0
15.0
20.0
25.0
2 2
As Above (SP-SM)
Boring B-3 Terminated at a Depth of 22 Feet Below Ground Surface.
As Above, Medium Dense (SP-SM)15 - 17 S-5 4 14
LACUSTRINE
8 - 10 S-4 2 2 24 4 As Above, Very Loose to Loose (SP-SM)
3 As Above (SP-SM)5 - 7 S-3 2 2 1 2 16
2 - 4 S-2 2 2 1
Brown, Very Loose, Poorly Graded Sand with Silt (SP-SM)
0 - 2 S-1 2 2
SUBSOIL 21" Subsoil, Roots
3 2 24 5
TS 9" Topsoil
2 17 3
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKSDepth
(feet)Blows Per 6"
Rec.
(in.)N (feet)(Classification)
--Equipment:Geoprobe 7822DT 24 Hours: --
Drill / Test Method:HSA / SPT (Autohammer)Contractor:CC --At Completion: --
Building Logged By:OR During:6.0
Elevation
22.0 feet bgs 11/8/2023
(feet bgs) (ft NAVD88) (feet bgs) (ft NAVD88)
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NS feet Above NAVD88 Date Started:11/8/2023 Water Depth Elevation Cave-In Depth
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
RECORD OF Boring No.: B-3
SUBSURFACE EXPLORATION Page of
DEPOSIT
20 - 22 S-6 7 8 16 21 15 24
8 2 16 22
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Boring Logs 10-8-23.xlsx 11/22/2023
1 1
Project:
Location:
Surface Elevation:±||
Termination Depth: Date Completed:| |
Proposed Location:| --
At Completion:| -- --|
| --24 Hours: --|
No Type
0.0
5.0
10.0
15.0
20.0
21.0
25.0
SUBSOIL 15" Subsoil, Roots
1/12"
TILL
Boring B-4 Terminated at a Depth of 22 Feet Below Ground Surface.
20 - 22 S-6 7 9 29 44 12 38
As Above (SP-SM)
GLACIAL Brown, Very Dense, Silty Sand with Gravel (SM)
16 1
15 - 17 S-5 6 11 8 7 18 19 As Above, Medium Dense (SP-SM)
10 - 12 S-5 1 1
3 As Above, Very Loose (SP-SM)
DEPOSIT
LACUSTRINE As Above (SP-SM)
8 - 10 S-4 3 1 2 1 14
6 As Above (SP-SM)5 - 7 S-3 3 3 3 3 16
2 10 52 - 4 S-2 2 3 2
Brown, Loose, Poorly Graded Sand with Silt (SP-SM)
0 - 2 S-1 1 2 2 2 15 4
TS 9" Topsoil
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKSDepth
(feet)Blows Per 6"
Rec.
(in.)N (feet)(Classification)
--Equipment:Geoprobe 7822DT 24 Hours: --
Drill / Test Method:HSA / SPT (Autohammer)Contractor:CC --At Completion: --
Building Logged By:OR During:5.5
Elevation
22.0 feet bgs 11/8/2023
(feet bgs) (ft NAVD88) (feet bgs) (ft NAVD88)
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NS feet Above NAVD88 Date Started:11/8/2023 Water Depth Elevation Cave-In Depth
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00
RECORD OF Boring No.: B-4
SUBSURFACE EXPLORATION Page of
NOTES: bgs = below ground surface, msl = mean sea level, NA = Not Applicable, NE = Not Encountered, NS = Not Surveyed, P = Perched RECORD OF SUBSURFACE EXPLORATION
WL Restaurant Brewery Saratoga Springs NY GM2321159.Y00 Boring Logs 10-8-23.xlsx 11/22/2023
1 1
Project:
Location:
Surface Elevation:±||
Termination Depth: Date Completed:| |
Proposed Location:| --
At Completion:| -- --|
| --24 Hours: --|
No Type
0.0
5.0
10.0
15.0
15 - 15.7 S-5 16 - 0 -
20.0
25.0
Boring B-5 Terminated at a Depth of 15.7 Feet Below Ground Surface.
No Recovery
8 - 10 S-4 4 1 1 1 14 2 As Above (SP-SM)
As Above (SP-SM)5 - 7 S-3 1 1 18 11/12"
1 18 22 - 4 S-2 2 1 1 Brown, Very Loose, Poorly Graded Sand with Silt (SP-SM)
0 - 2 S-1 2 2
SUBSOIL 12" Subsoil, Roots
3 2 20 5
TS 9" Topsoil
SAMPLE INFORMATION DEPTH STRATA DESCRIPTION OF MATERIALS REMARKSDepth
(feet)Blows Per 6"
Rec.
(in.)N (feet)(Classification)
--Equipment:Geoprobe 7822DT 24 Hours: --
RECORD OF Boring No.: B-5
SUBSURFACE EXPLORATION Page of
Elevation
15.7 feet bgs 11/8/2023
(feet bgs) (ft NAVD88) (feet bgs) (ft NAVD88)
3376 South Broadway, Saratoga Springs, Saratoga County, New York Client:WL Enterprises Asquisitions, LLC
NS feet Above NAVD88 Date Started:11/8/2023 Water Depth Elevation
40/2"
LACUSTRINE
DEPOSIT
Proposed Brewery/Restaurant WAI Project No.:GM2321159.Y00